Manual
7-2
IM 04L21B01-01EN
Setup Items
• Logic box number
You can set up to 40.
• Event action > Event
The condition to execute the action.
Settings Description
None Not use.
Remote Select the remote control input terminal number.
Relay Select the alarm output relay number. During Edge operation, a change
from deactivated to activated is an event.
Switch Select the internal switch number. During Edge operation, a change from off
to on is an event.
Timer Select the timer number.
Matchtime Select the match timer number.
Alarm During Edge operation, a change from “no alarms are active” to “at least
one alarm is active” is an event.
USER key -
• Event action > Action
The action to be executed when an event occurs.
Settings Description
Memory -
Start -
Stop -
Trigger Can be specified when the FX is configured to record event data.
AlarmACK Cannot be specified when the event is set to Relay, Switch, or Alarm.
Math Can be specified on FXs with the /M1, /PM1, or /PWR1 option.
MathStrt Start computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.
MathStop Stop computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.
Math rst Reset computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.
SaveDisp Can be specified when the FX is configured to record display data.
SaveEvt Can be specified when the FX is configured to record event data.
Message Set the message number to write the message and the destination. Set the
message destination to all groups (All) or a group number.
Snap Snapshot
Rate1/2 Can be specified when the function for switching between the trend interval and
the secondary trend interval is enabled.
M.sample Manual sampling
TimerRst Cannot be specified when the event is set to Timer.
Group Specify the number of the group to be displayed.
Flag Can be specified on FXs with the /M1, /PM1, or /PWR1 option.
Time adj Can be specified only when the event is set to Remote.
PnlLoad Can be specified only when the event is set to Remote.
7.1 Setting the Event Action Function
(Including the remote control function of the /R1 and /PM1 options and the USER key)