Manual
6-2
IM 04L21B01-01EN
• Recording Conditions of Event Data
*
Press MENU (to switch to setting mode), and select the Menu tab > Data save >
Event data.
* When you set the type of data that you want to save to “Display,” which is the default value,
“Event data” is not displayed in the sub menu. Change the Data kind setting on the A/D,
Memory screen in basic setting mode.
Setup Items
• Memory > Data kind
Settings Description
Display Records display data.
E+D Records display data and event data. This setting cannot be selected when
the trend interval switching function is set to On.
Event Records event data.
• Memory sample > On/Off
Turn On the target channels.
Settings Description
On Measured data is recorded. Waveforms are displayed on the trend display.
Off Measured data is not recorded. Even when registered in a display group,
waveforms are not displayed in the trend display.
• Trend/Save interval > Trend interval [/div] (when recording display data)
See the table below. You can only set trend intervals that are longer than the scan
interval you set in Basic Setting Mode.
• Trend/Save interval > Save interval (when recording display data)
Select the size of a record data le. The recorded data is divided by the le size
specied here. The available settings vary depending on the number of memory
sampling channels and the Trend interval setting.
Trend interval
1
15 s
2
30 s 1 min 2 min 5 min
Sample rate 500 ms 1 s 2 s 4 s 10 s
Selectable range
of save interval
10 min to
3 days
10 min to
7 days
10 min to
14 days
10 min to
14 days
10 min to
31 days
Trend interval
1
10 min 15 min 20 min 30 min 1 h
Sample rate 20 s 30 s 40 s 1 min 2 min
Selectable range
of save interval
10 min to
31 days
10 min to
31 days
1 hour to
31 days
1 hour to
31 days
1 hour to
31 days
Trend interval
1
2 h 4 h 10 h
Sample rate 4 min 8 min 20 min
Selectable range
of save interval
2 hours to
31 days
4 hours to
31 days
8 hours to
31 days
1 You cannot set a trend interval that corresponds to a sampling interval that is faster than the
scan interval.
2 Selectable on the FX1002 and FX1004
• Trend/Save interval > Second interval [/div]
See section 5.3.
6.1 Setting the Recording Conditions of the Measured Data