Operation Manual
5-5
IM 1F5B2-01E
5. WIRING
IMPORTANT
■ALWAYS waterproof all threaded parts. (A silicon-resin, non-hardening sealing
material is recommended for the waterproof treatment.)
Table 5.3 Types of Packings and Applicable Outer Diameters of Cables
edoCxiffuS
daerhTforetemaiD
troPgniriWno
elbacilppAforetemaiDretuO
)mm(elbaC
noitacifitnedI
gnikraM
rebmuNtraP
5GP2/1G
9ot5.8
01ot1.9
11ot1.01
9 φ
01 φ
11 φ
DA1069G
5.4 Grounding
■ For an analog output application, connect a grounding wire from ULTRA YEWFLO
to the ground.
■ For a pulse output application, connect a grounding wire from ULTRA YEWFLO to
the ground. Also ground the shielded cable that connects ULTRA YEWFLO to the
pulse receiver.
■ Use the Class 3 Grounding method (grounding resistance of no greater than 100 Ω).
■ Use a 600V grade polyvinyl chloride insulated wiring for grounding.