Operation Manual
4-10
IM 1F5B2-01E
IMPORTANT
• In vertical mounting, ALWAYS make sure ULTRA YEWFLO is mounted with the
wiring port facing downward, as shown in Figure 4.2-3, to prevent against the ingress
of rainwater, etc.
4.2.2 Installing a Flange Type of ULTRA YEWFLO
• Using stud bolts, nuts and gaskets, install ULTRA YEWFLO as shown in Figures 4.2-
5 and 4.2-6.
• It is always the user’s responsibility to procure gaskets for flowmeter mounting (see
Figure 4.2-1). (In order to prevent gaskets from protruding into the flow path, use
gaskets with pre-cut bolt holes whenever possible.)
IMPORTANT
• Use gaskets whose inner diameter is greater than those of ULTRA YEWFLO and the
joint pipe. Exercise extreme care to prevent the gaskets from protruding into the flow
path.
Direction
of flow
Nut
Bolt
Gasket
Figure 4.2-5 Horizontal Mounting
IMPORTANT
• In vertical mounting, ALWAYS make sure ULTRA YEWFLO is mounted with the
wiring port facing downward, as shown in Figure 4.2-3, to prevent against the ingress
of rainwater, etc.