4. MOUNTING
• When pulsating pressure caused by a T-type piping exist, install the valve on the
upstream of the flowmeter.
Example: As shown in the figure below, when the valve V1 is turned off, the fluid
flow through B, as to meter A the flow is zero. But due to the pulsating
pressure is detected, the meterís zero point become fluctuating. To avoid
this, change the valve V1 location to V1’.
A
V1V1'
Valve (Off)
Flow
B
Relocating
Figure 4.1-4b Piping where Paulsating Pressure Caused by a T-type Piping
■ Piping That Prevents Cavitation from Occurring
IMPORTANT
• Avoid mounting ULTRA YEWFLO with its downstream side open to the atmosphere.
Otherwise, there will be an increased risk of cavitation.
■ The case of downstream open to the air:
If downstream open to the air, the cavitation possibly occurs. Avoid this kind use.
If such piping cannot avoid, up and down the downstream pipe as shown the figure
below, or, install a valve on the downstream side.
Installation Example
P
Pump
Tank
Tank
Figure 4.1-5 Piping when downstream open to the air
■ Joint Pipes
For joint pipes, use pipes with an inner diameter greater than that of ULTRA YEWFLO
(use pipes with a schedule number no larger than 80 for joint pipes with a nominal inner
diameter ranging from 25 mm to 100 mm).
IMPORTANT
• Exercise care to prevent the gaskets inserted between ULTRA YEWFLO and the joint
pipes from protruding into the flow path.