User guide
2-28
IM 04L51B01-17EN
p3 P4 p5 p6
Event Type Value Source
Element
Number
Alarm
Level
Operation
mode
Internal Switch SW 1 to 100 - Rising, Falling,
Both
Remote control input DI Channel
number
- Rising, Falling,
Both
Relay (DO channel) DO Channel
number
- Rising, Falling,
Both
Alarm
(I/O channel)
AlarmIO Channel
number
1 to 4 Rising, Falling,
Both
Alarm
(math channel)
AlarmMath Channel
number
1 to 4 Rising, Falling,
Both
Alarm
(communication
channel)
AlarmCom Channel
number
1 to 4 Rising, Falling,
Both
Alarm AlarmAll - - Rising, Falling,
Both
Timer Timer 1 to 4 - Edge
Match time timer MatchTimeTimer 1 to 4 - Edge
Conditions p7 p8 p9 p10
p6 Action Type Value Source
Element
Number
Action
Detail 1
Action
Detail 2
Rising,
Falling,
Edge
Recording Memory - Start, Stop -
Math (math channel) Math - Start,
Stop,
Reset
-
Display rate switch RateChange 1, 2 - -
Flag Flag 1 to 20 - -
Manual sample ManualSample - - -
Alarm ACK AlarmACK - - -
Snapshot Snapshot - - -
Time adjustment TimeAdjust - - -
Display data save SaveDisplay - - -
Event data save SaveEvent 1 - -
Event trigger Trigger 1 - -
Message Message 1 to 100 All, Select 1 to 50
Display group
change
GroupChange 1 to 50 - -
Relative timer reset TimerReset 1 to 4 - -
Settings load ConfigLoad 1 to 3 - -
Favorite screen
display
PlayList 1 to 20 - -
Both Recording start/stop MemoryStartStop - - -
Math start/stop MathStartStop - - -
Display rate switch
1/2
RateChange1_2 - - -
Flag On/Off FlagOn_Off 1 to 20 - -
Query
SEventAct[,p1]?
Invalid parameters are returned as blanks in
queries.
Example Execute memory start on the rising edge of the
remote control input (channel 0101). Use event
action number 2.
SEventAct,2,On,DI,0101,,Rising,Mem
ory,,Start
Description
• There are limitations to event and action
combinations. For details, see section 1.14 in the
Models GX10/GX20/GP10/GP20 Paperless Recorder
User’s Manual (IM 04L51B01-01EN).
• Write only delimiters (commas) for irrelevant
parameters (invalid even if a value is specified).
• Event type “DI” is the channel of the DI module that
has been set to remote module (SModeDI command).
• Math channel and flag are an option (/MT).
• Communication channels are an option (/MC).
SReport
Report Type (/MT)
Sets the type of report to create.
No Reports
Syntax
SReport,p1
p1
Type (Off)
Hourly and Daily Reports
Syntax
SReport,p1,p2
p1
Type (Hour+Day)
p2
Time to create reports: Hour (HH) (00 to
23)
Daily and Weekly Reports
Syntax
SReport,p1,p2,p3
p1
Type (Day+Week)
p2
Day to create reports (Mon, Tue, Wed, Thu,
Fri, Sat, Sun)
p3
Time to create reports: Hour (HH) (00 to
23)
Daily and Monthly Reports
Syntax
SReport,p1,p2,p3
p1
Type (Day+Month)
p2
Day to create reports (1 to 28)
p3
Time to create reports: Hour (HH) (00 to
23)
Batch Reports
Syntax
SReport,p1,p2
p1
Type (Batch)
p2
Recording interval (10min, 15min, 30min,
1h)
Day Custom Reports
Syntax
SReport,p1,p2,p3,p4,p5
p1
Type (Custom)
p2
Recording interval (10min, 15min, 30min,
1h)
p3
File creation interval (4h, 6h, 8h, 12h, 24h)
P4
Time to create reports: Hour (HH) (00 to
23)
p5
Time to create reports: Minute (MM) (00
to 59)
Query
SReport[,p1]?
Example Create daily reports at 09:00 every day and
monthly reports at 09:00 on the first day of
each month.
SReport,Day+Month,1,09
Description
• You cannot use this command to configure settings
while recording is in progress.
• You cannot use this command to configure settings
while computation is in progress.
• If p1=Off, you cannot set p2 or subsequent
parameters.
SRepData
Report Data (/MT)
Sets the data type and file type of reports.
Syntax
SRepData,p1,p2,p3,p4,p5,p6
p1
Data type 1 (Max, Min, Ave, Sum, Inst)
p2
Data type 2 (Off, Max, Min, Ave, Sum,
Inst)
p3
Data type 3 (Off, Max, Min, Ave, Sum,
Inst)
2.4 Setting Commands