User guide

2-14
IM 04L51B01-17EN
p2=Volt p2=TC p2=RTD p2=GS p2=DI
20mV R Pt100 1-5V Level
60mV S Pt100-H 0.4-2V DI
200mV B JPt100
1V K JPt100-H
2V K-H Cu10GE
6V E Cu10LN
20V J Cu10WEED
50V T Cu10BAILEY
N Cu10a392
W Cu10a393
L Cu25
U Cu53
PLATINEL Cu100
PR20-40 J263B
WRe3-25 Ni100SAMA
KpvsAu7Fe Ni100DIN
NiNiMo Ni120
WWRe26 Pt25
N14 Pt50
XK Pt200WEED
Cu10G
Cu50G
Cu100G
Pt46G
Pt100G
SRangeDI
Measurement Range of DI Channel
Sets the measurement range of a DI channel.
Unused Channels
Syntax
SRangeDI,p1,p2
p1
Channel number
p2
Input type (Skip)
Channels That Are Not Delta or Scaling
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Off)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
Delta Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Delta)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
p7
Reference channel number
Scaling Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10
p1
Channel number
p2
Input type (DI)
p3
Fixed at “-.”
P4
Calculation type (Scale)
p5
Span lower limit (0 to 1)
p6
Span upper limit (0 to 1)
p7
Decimal Place (0 to 5)
p8
Scaling lower limit
p9
Scaling upper limit
p10
Unit (up to 6 characters, UTF-8)
Query
SRangeDI[,p1]?
Example Measure 0 to 1 on channel 0103. No scaling.
SRangeDI,0103,DI,-,Off,0,1
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
SRangeDO
DO Channel Operation
Sets the DO channel operation.
Alarm Output
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1
Channel number
p2
Output type (Alarm)
p3
Span lower limit (0 to 1)
P4
Span upper limit (0 to 1)
p5
Unit (up to 6 characters, UTF-8)
p6
Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_energize
De-energize the relay
(DO channel) during
output.
p7
Operation
And
Operate when all set alarms are
in the alarm state.
Or
Operate when any of the set
alarms are in the alarm state.
p8
Hold or nonhold
Hold
Hold output until an
alarm ACK operation.
Nonhold
Clear output when the
alarm is cleared.
p9
Relay (DO channel) action on
acknowledge (Normal, Reset)
Alarm Output (Reflash)
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1
Channel number
p2
Output type (Alarm)
p3
Span lower limit (0 to 1)
P4
Span upper limit (0 to 1)
p5
Unit (up to 6 characters, UTF-8)
p6
Energize or de-energize
Energize
Energize the relay (DO
channel) during output.
De_energize
De-energize the relay
(DO channel) during
output.
p7
Action (Reflash)
p8
Reflash time (500ms, 1s, 2s)
2.4 Setting Commands