Manual

1-49
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
1.5.2 Setting Expressions
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Math channel settings >
Calculation expression
Web browser: Config. tab > Math channel settings > Math channel settings > Channel
range (display example: A001-A020)
Hardware configurator: Math channel settings > Math channel settings >Channel range
(display example:A001-A020)
Description
Setup Item Selectable Range or Options Default Value
First-CH GX20/GP20: A001 to A100
GX10/GP10: A001 to A050
A001
Last-CH Same as the first channel A001
First-CH, Last-CH
Set the target channels.
Math range
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
Calculation expression
1
Character string (up to 120 characters) 001
Decimal place
1
0, 1, 2, 3, 4, 5 2
Span Lower
1
–9999999 to 99999999 0.00
Span Upper
1
–9999999 to 99999999 100.00
Unit
1
Character string (up to 6 characters,
A
a
#
1
)
1 Appears when On/Off is set to On.
On/Off
Set the channels that you want to use to On.
Computation is performed every scan interval, starting with the smallest channel number.
Example: If you specify A002=A001+A003, the value of the previous scan interval is used for
A003.
Calculation expression
Set the expression.
In computations, measured values are handled as values without units. For example, if the
measured data from channel 0001 is 20 mV and the measured data from channel 0002 is
20 V, the computed result of 0001 + 0002 is 40.
1.5 Configuring Math Channels