Manual

17
<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation
GS 04L52B01-01EN May. 7, 2013-00
DIGITAL OUTPUT MODULE (Model
GX90YD, or Options /CR1x, /CR2x,
/CR4x)
GX90YD
Application: Alarm output, etc
Number of outputs: 6
Output update interval: 100 ms (shortest)
Output type: Relay contact output, SPDT (NO-C-
NC)
Insulation type: Mechanical
Rated load voltage: 24 V DC or 250 V AC or less
Rated load current: 3 A (DC)/3 A (AC), resistance
load, each channel
Min. load voltage/current: 5 V DC
Recommended replacement periods of contact:
Mechanical 5,000,000 more ON-OFF operations
Electrical 30,000 more ON-OFF operations (250
V AC 3 A or 24 V DC 3 A, resistance load)
Number of common: 6
Power supply: Not necessary
Terminal type: M3 screw terminal
Withstand voltage
Between the output terminals and the internal
circuit: 3000 V AC for one minute
Insulation resistance:
Between the output terminals and the internal
circuit: 20 MΩ or greater at 500 VDC
Safety and EMC Standards
Safety and EMC Standards: Same as the digital
input module
WEEE Directive: Compliant
Construction
Front panel (terminal): Water and dust-proof,
Complies with IEC529-IP20
Material: Polycarbonate
Color;
Front: Charcoal grey light (CC28)
Bezel: Smoke blue (CC53)
Dimensions: 45 mm(W) x 100 mm(H) x 133
mm(D) (D: including terminal cover)
Weight: Approx. 0.3 kg
Power Supply
Suppy from GP main unit.
Power consumption: 1.4 W or less
Terminal arrangements
M3 screw terminal
No. Symbol No. Symbol
21 DO4 N.C. 11 DO1 N.C.
22 DO4 COM 12 DO1 COM
23 DO4 N.O. 13 DO1 N.O.
24 DO5 N.C. 14 DO2 N.C.
25 DO5 COM 15 DO2 COM
26 DO5 N.O. 16 DO2 N.O.
27 DO6 N.C. 17 DO3 N.C.
28 DO6 COM 18 DO3 COM
29 DO6 N.O. 19 DO3 N.O.
30 - 20 -
External Dimensions
M3 screw terminal
97.1(3.82)
82.1(3.23)
36
(1.42)
92(3.62)
100(3.94)
3(0.12)
8(0.31)
(0.07)
1.9
45.1(1.78)
31.9(1.26)
Unit: mm
(approx. inch)