DIGITAL OUTPUT MODULE (Model
GX90YD, or Options /CR1x, /CR2x,
/CR4x)
GX90YD
• Application: Alarm output, etc
• Number of outputs: 6
• Output update interval: 100 ms (shortest)
• Output type: Relay contact output, SPDT (NO-C-
NC)
• Insulation type: Mechanical
• Rated load voltage: 24 V DC or 250 V AC or less
• Rated load current: 3 A (DC)/3 A (AC), resistance
load, each channel
• Min. load voltage/current: 5 V DC
• Recommended replacement periods of contact:
Mechanical 5,000,000 more ON-OFF operations
Electrical 30,000 more ON-OFF operations (250
V AC 3 A or 24 V DC 3 A, resistance load)
• Number of common: 6
• Power supply: Not necessary
• Terminal type: M3 screw terminal
• Withstand voltage
Between the output terminals and the internal
circuit: 3000 V AC for one minute
• Insulation resistance:
Between the output terminals and the internal
circuit: 20 MΩ or greater at 500 VDC
Safety and EMC Standards
• Safety and EMC Standards: Same as the digital
input module
• WEEE Directive: Compliant
Construction
• Front panel (terminal): Water and dust-proof,
Complies with IEC529-IP20
• Material: Polycarbonate
• Color;
Front: Charcoal grey light (CC28)
Bezel: Smoke blue (CC53)
• Dimensions: 45 mm(W) x 100 mm(H) x 133
mm(D) (D: including terminal cover)
• Weight: Approx. 0.3 kg
Power Supply
Suppy from GP main unit.
• Power consumption: 1.4 W or less
Terminal arrangements
M3 screw terminal
No. Symbol No. Symbol
21 DO4 N.C. 11 DO1 N.C.
22 DO4 COM 12 DO1 COM
23 DO4 N.O. 13 DO1 N.O.
24 DO5 N.C. 14 DO2 N.C.
25 DO5 COM 15 DO2 COM
26 DO5 N.O. 16 DO2 N.O.
27 DO6 N.C. 17 DO3 N.C.
28 DO6 COM 18 DO3 COM
29 DO6 N.O. 19 DO3 N.O.
30 - 20 -
External Dimensions
M3 screw terminal
97.1(3.82)
82.1(3.23)
36
(1.42)
92(3.62)
100(3.94)
3(0.12)
8(0.31)
(0.07)
1.9
45.1(1.78)
31.9(1.26)
Unit: mm