OVERVIEW
The GP10/GP20 are portable type paperless recorders
that display real-time measured data on a touch
screen and save data on an external storage medium
(SD card).
The number of measurement data is a maximum
of 48 channels in GP10, and a maximum of 100
channels in GP20.
The GP10/GP20 have the large internal memory
(GP10/GP20: 500MB), and prolonged record and
preservation are possible.
As the input signal, a DC voltage, thermocouple,
resistance temperature detector, or contact signal
can be set to each channel.
Input and output have module structure and it can
extend them easily. (GP10: max. 3, GP20: max. 10)
A module type is three types, an analog input, a
digital input, and a digital output.
The intuitive operation by ick, pinch in, pinch out,
and swipe are possible.
The past trend under recording can be seamlessly
displayed on a trend screen.
Moreover, the measurement data of the time
specied on the calendar screen can be searched
and displayed.
Various functions, such as a freehand message,
a PDF/Excel output of a report le, a direct output
to a network printer, a scale movement of a trend
display, and a buzzer sound, are equipped.
It can be hooked up to network via Ethernet, which
enables to inform by Email and to monitor on Web
site as well as to transfer les by using FTP. Also,
it can communicate with Modbus/RTU or Modbus/
TCP.
A setup of GP can be performed on-line from the
web browser on PC. A setup by off-line is also
possible.
Universal Viewer software allows a PC to
display waveforms on its screen and to print out
waveforms.
MAIN UNIT SPECIFICATIONS
FUNCTIONAL SPECIFICATION
Input Specications
Please see "INPUT/OUTPUT MODULE
SPECIFICATIONS."
Display Functions
Display groups:
Number of groups; GP10: 30, GP20: 50
Number of channels that can be assigned to
each group; GP10: 10, GP20: 20
Scan interval: 100*, 200*, 500 ms*, 1, 2, 5 s
* Cannot be specied if an electromagnetic relay
scanner type (Type Sufx Code: -T1) analog input
module is in use.
Display color (Trend/Bar graph/Digital display):
Channel: Select from 24 colors
A desired display color can be selected freely
using its RGB value.
Background: Select from white or black
Display type:
Trend display (T-Y)
Display method:
Direction: Horizontal, vertical
Trend interval: 5*, 10*, 15*, 30 s/div, 1, 2, 5,
10, 15, 20, 30 min/div, 1, 2, 4, 10 h/div
* Cannot be specied if an electromagnetic relay
scanner type analog input module is in use.
Trend line width: Thick, normal, thin
Scale; GP10: Max. 6, GP20: Max. 10
Current value bar graph, color scale band,
and alarm point marks can be displayed on
the scale.
Moving scale; Scale can be moved on any
waveform.
A bitmap image scale can be attached.
Others; Grid (Auto, 4 to 12), Trip line, Message,
Zone display, Partial expanded display
Historical trend display (T-Y display)
Redisplays the display data or event data in the
internal memory or external storage medium
Time axis operation: The time axis can be
reduced or expanded.
Data search: Waveforms from the internal
memory can be displayed through the
specication of a date and time, calendar, each
summary
Moving scale; A bitmap image scale can be
attached.
All historical trends can be displayed in one
screen.
Bar graph display
Direction: Vertical or horizontal
Scale: Display a scale for each channel
Color scale band, and alarm point marks can
be displayed on the scale.