GS 04L51B01-01EN May. 7, 2013-00
Noise reduction ratio
Integration time
*1
Normal mode Common mode
1.67 ms 50/60 Hz, no noise
reduction
More than 80 dB
*2
*4
More than 16.7 ms More than 40 dB
*2
*3
More than 120 dB
*2
*4
*1 A frequency discrimination setting is made in the
main unit.
*2 A resistance temperature detector range is a
converted value of voltage when a measured
current ows.
*3 50/60 Hz ± 0.1 %
*4 50/60 Hz ± 0.1%, 500 Ω imbalance, between
minus measuring terminal and ground
Normal mode voltage for TC/ DC voltage (1 V
range or less)/DI: 1.2 times or less of rated range
Standard signal 0.4 to 2 V range: 2.4 V
Standard signal 1-5 V range: 6 V
RTD (100 Ω): 50 mV peak
RTD (50 Ω): 10 mV peak
* 50/60Hz, The peak value including the signal.
Maximum common mode voltage for measuring
input: 30 V ACrms (50/60Hz) or 60 V DC
(However, maximum common mode noise
voltage for measuring input: 250 V ACrms)
Maximum voltage between measuring input
channels: 30 V ACrms (50/60 Hz) or 60 V DC
(maximum common mode noise voltage for
measuring input: 250 V ACrms)
Reference junction compensation accuracy:
When measuring temperature greater than
or equal to 0 °C and when input terminal
temperature is balanced
Type K, E, J, T, N, XK GOST: ±0.5 °C (23 °C ± 2
°C), ±0.7 °C (0 to 50 °C), ±1.0 °C (-20 to 60 °C)
Type R, S, W, L, U, W97Re3-W75Re25,
Platinel2, NiNiMo, W/WRe26, N(AWG14): ±1.0
°C (23 °C ± 2 °C), ±1.4 °C (0 to 50 °C), ±2.0 °C
(-20 to 60 °C)
Type KpvsAu7Fe: ±1.0 K (23 °C ±2 °C), ±1.4 K
(0 to 50 °C), ±2.0 K (-20 to 60 °C)
Type B, PR20-40: Internal reference
compensation is xed to 0°C
Sampling interval/A/D integration time:
10 ch. mode
Solid state relay scanner type*1
Sampling interval Integration time
100 ms/200 ms 1.67 ms
500 ms or more 16.7 ms/20 ms
1 s or more 36.7 ms
2 s or more 100 ms
Electromagnetic relay scanner type
Sampling interval Integration time
1 s or more 16.7 ms/20 ms
2 s or more 36.7 ms
5 s 100 ms
2 ch. mode
*2
Sampling interval Integration time
100 ms or more 16.7 ms/20 ms
1 s or more 36.7 ms
2 s or more 100 ms
*1 In 10ch mode, when the scan interval is set to 100
ms or 200 ms, the A/D integration time is xed at
1.67 ms. This prevents power frequency noise
from being eliminated, causing measured values
to wobble.
*2 Cannot be specied for the electromagnetic relay
scanner type (Type Sufx Code: -T1).
Calibration correction:
Mode: Linearizer Approximation, Linearizer Bias
Number of set points: 12
Terminal type*: M3 screw terminal or Clamp terminal
* M3 screw terminals only for the electromagnetic
relay scanner type.
Withstand voltage
Between the input circuits and the internal circuit:
3000 V AC for one minute
Between the analog input channels: 1000 V AC
for one minute (excluding b-terminal)
Insulation resistance:
Between the input terminal and the internal
circuit: 20 MΩ or greater at 500 VDC
Recommended replacement period of
electromagnetic relay scanner type modules:
Electromagnetic relay scanner type modules
make measurements by switching mechanical
contact relays on and off.
To ensure that the modules continue to operate
reliably and correctly, replace them
Continuous use at measurement interval 1 s: 1 year
Continuous use at measurement interval 2 s: 2 years
Continuous use at measurement interval 5 s: 5 years
Safety and EMC Standards
CSA: CSA22.2 No.61010-1, installation category
II (*1), pollution degree 2 (*2), and CSA-C22.2
NO. 61010-2-030-12
UL: UL61010-1, UL 61010-2-030 (CSA NRTL/C)
CE:
EMC directive
EN61326-1 compliance, Class A Table 2
EN61000-3-2 compliance
EN61000-3-3 compliance
EN55011 Class A Group 1
Low voltage directive
EN61010-1, EN 61010-2-030
Installation category II (*1)
Pollution degree 2 (*2)
Measurement category II (*3)
Maximum input voltage for measuring input: ± 60 V DC
Maximum common mode noise voltage for
measuring input: 30 V ACrms 50/60 Hz or 60 V
DC (However, maximum common mode noise
voltage for measuring input: 250 V AC)
C-Tick: EN55011 compliance, Class A Group 1
KC marking: Electromagnetic wave interference
prevention standard, electromagnetic wave
protection standard compliance
*1 Installation category (overvoltage category) II:
Describes a number which denes a transient
overvoltage condition.