INPUT/OUTPUT MODULE SPECIFICATIONS
ANALOG INPUT MODULE (Model GX90XA or Option /Uxx0)
• Number of inputs: 10
• Input Type: DC voltage, standard signal, thermocouple (TC), resistance
temperature detector (RTD)
*1
, ON/OFF input (DI), and DC current (by adding an
external shunt resistor)
• Measurement interval: 100
*1
, 200
*1
, 500 ms
*1
, 1, 2, 5 s
• Input range: -5% or more and 105% or less (accuracy is guaranteed in the range
from 0% to 100% inclusive)
• Measurement ranges and accuracies
*2
(However, the number of display digits can
be increased by scaling.)
*1
Cannot be specied for the electromagnetic relay scanner type (Type Sufx Code: -T1).
*2
The following specications apply to operation of the recorder under standard operation conditions.
Temperature: 23 ± 2 °C, Humidity: 55% ± 10% RH, Power supply voltage: 90 to 132 or
180 to 250 VAC, Power supply frequency: 50/60 Hz ± 1%, Warm-up time: At least 30 min.
Other ambient conditions such as vibration should not adversely affect recorder operation.
Input Type Range Measurement accuracy (digital display) Max. resolution
of digital display
A/D integration time: 16.7ms or more A/D integration time: 1.67ms
DCV 20 mV -20.000 to 20.000 mV ±(0.05 % of rdg + 12 μV) ±(0.1 % of rdg + 40 μV) 1 μV
60 mV -60.00 to 60.00 mV ±(0.05 % of rdg + 0.03 mV) ±(0.1 % of rdg + 0.15 mV) 10 μV
200 mV -200.00 to 200.00 mV ±(0.05 % of rdg + 0.03 mV) ±(0.1 % of rdg + 0.4 mV) 10 μV
1 V -1.0000 to 1.0000 V ±(0.05 % of rdg + 1.2 mV) ±(0.1 % of rdg + 4 mV) 100 μV
2 V -2.0000 to 2.0000 V ±(0.05 % of rdg + 1.2 mV) ±(0.1 % of rdg + 4 mV) 100 μV
6 V -6.000 to 6.000 V ±(0.05 % of rdg + 3 mV) ±(0.1 % of rdg + 15 mV) 1 mV
20 V -20.000 to 20.000 V ±(0.05 % of rdg + 3 mV) ±(0.1 % of rdg + 40 mV) 1 mV
50 V -50.00 to 50.00 V ±(0.05 % of rdg + 0.03 V) ±(0.1 % of rdg + 0.15 V) 10 mV
Standard
signal
0.4-2V 0.3200 to 2.0800 V ±(0.05 % of rdg + 1.2 mV) ±(0.1 % of rdg + 4 mV) 100 μV
1-5V 0.800 to 5.200 V ±(0.05 % of rdg + 3 mV) ±(0.1 % of rdg + 15 mV) 1 mV
TC
(Excluding
RJC
accuracy)
R 0.0 to 1760.0 °C ±(0.15 % of rdg + 1.0 °C)
However, R, S; 0.0 to 800.0 °C: ±2.2 °C,
B; 400.0 to 800.0 °C: ±3.0 °C
Accuracy at less than 400.0 °C is not guaranteed.
±(0.2 % of rdg + 6.0 °C)
However, R, S; 0.0 to 800.0 °C: ±7.6 °C,
B; 400.0 to 800.0 °C: ±11.0 °C
Accuracy at less than 400.0 °C is not guaranteed.
0.1 °C
S 0.0 to 1760.0 °C
B 0.0 to 1820.0 °C
K -270.0 to 1370.0 °C ±(0.15 % of rdg + 0.7 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.7 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 5.0 °C)
However, -200.0 to 0.0 °C: ±(3 % of rdg + 5.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
-200.0 to 500.0 °C
E -270.0 to 800.0 °C ±(0.15 % of rdg + 0.5 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 4.0 °C)
However, -200.0 to 0.0 °C: ±(2 % of rdg + 4.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
J -200.0 to 1100.0 °C
T -270.0 to 400.0 °C ±(0.15 % of rdg + 0.5 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 2.5 °C)
However, -200.0 to 0.0 °C: ±(2 % of rdg + 2.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
N -270.0 to 1300.0 °C ±(0.15 % of rdg + 0.7 °C)
However, -200.0 to 0.0 °C: ±(0.7 % of rdg + 0.7 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.3 % of rdg + 6.0 °C)
However, -200.0 to 0.0 °C: ±(5 % of rdg + 6.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
W 0.0 to 2315.0 °C ±(0.15 % of rdg + 1.5 °C) ±(0.3 % of rdg + 14.0 °C)
However, more than 1000.0 °C: ±(0.8 % of rdg
+ 9.0 °C)
0.1 °C
L -200.0 to 900.0 °C ±(0.15 % of rdg + 0.5 °C)
Less than 0.0 °C: ±(0.5 % of rdg + 0.5 °C)
±(0.2 % of rdg + 4.0 °C)
Less than 0.0 °C: ±(3 % of rdg + 4.0 °C)
0.1 °C
U -200.0 to 400.0 °C ±(0.15 % of rdg + 0.5 °C)
Less than 0.0 °C: ±(0.7 % of rdg + 0.5 °C)
±(0.2 % of rdg + 2.5 °C)
Less than 0.0 °C: ±(3 % of rdg + 2.5 °C)
0.1 °C
W97Re3-
W75Re25
0.0 to 2320.0 °C ±(0.2 % of rdg + 2.5 °C) ±18.0 °C
More than 2000.0 °C: ±0.9 % of rdg
0.1 °C
KpvsAu7Fe
0.0 to 300.0 K ±(0.15 % of rdg + 2.0 K)
0.15 to 280.15K: guaranteed range
±(0.2 % of rdg + 7.0 K)
0.15 to 280.15K: guaranteed range
0.1 K
Platinel 2 0.0 to 1395.0 °C ±(0.25 % of rdg + 2.3 °C) ±(0.25% of rdg + 8.0 °C) 0.1 °C
PR20-40 0.0 to 1900.0 °C
±(0.7 % of rdg + 0.4 °C)
However, accuracy at less than 800.0 °C is not
guaranteed.
±20.0 °C
However, accuracy at less than 800.0 °C is not
guaranteed.
0.1 °C
NiNiMo 0.0 to 1310.0 °C ±(0.25 % of rdg + 0.7 °C) ±(0.5% of rdg + 5.0 °C) 0.1 °C
W/
WRe26
0.0 to 2320.0 °C
±(0.2 % of rdg + 2.0 °C)
However, accuracy at less than 300.0 °C is not
guaranteed.
±(0.4 % of rdg + 12.0 °C)
However, accuracy at less than 300.0 °C is not
guaranteed.
0.1 °C
N(AWG14)
0.0 to 1300.0 °C ±(0.2 % of rdg + 1.3 °C) ±(0.5% of rdg + 7.0 °C) 0.1 °C
XK GOST
-200.0 to 600.0 °C ±(0.25 % of rdg + 0.8 °C) ±(0.5% of rdg + 4.0 °C) 0.1 °C
GX90XA