Manual

4
All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 04L51B01-01EN May. 7, 2013-00
Clock Functions
Clock: With a calendar function
Accuracy: ± 5 ppm (0 to 50°C), excluding a delay
(of 1 second, maximum) caused each time the
power is turned on.
Time setting: Using touch operation,
communication command, event action function,
or SNTP client function
Time adjustment method:
Limit in which the time is gradually adjusted:
Select from the available settings between 5 s
and 15 s.
Whether to change an out-of-limit operation
immediately or report it as an error can be
selected.
While memory sampling: Corrects the time by 1
ms for each second.
While memory is stopped: Immediately change
the time.
DST: The date/time for switching between
standard time and DST can be specied.
Time zone: Sets the time difference from GMT.
Date format: Select "YYYY/MM/DD", "MM/DD/
YYYY", "DD/MM/YYYY" or "DD.MM.YYYY".
MM expression can be selected from the
numeric character or ellipsis. Ex. January: 01 or
Jan
The delimiter can be selected from "/", ".", "-".
Ethernet Communication Functions
Electrical specications: Conforms to IEEE 802.3
Connection: Ethernet (10BASE-T/100BASE-TX)
Max. segment length: 100 m
Max. connecting conguration: Cascade Max. 4
level (10BASE-T), Max. 2 level (100BASE-TX)
Connector: RJ-45
Protocols: TCP, UDP, IP, ICMP, ARP, DHCP,
HTTP, FTP, SMTP, SNTP, Modbus, and
dedicated protocols
E-mail client: Automatically send e-mail at
specied times.
E-mail is sent by events as below.
- Alarm occurring/alarm canceling
- Recover from power failure
- Report data generating
- Storage medium error, FTP client function
error
- Specied time period
POP before SMTP and SMTP authentication
(PLAIN and CRAM-MD5) is available.
FTP client: Automatically transfer data les to the
FTP server.
Applicable les: Display data, event data, screen
image data, report data, etc.
FTP Server: Transfer les, delete les,
manipulate directories, and output le lists of the
GX.
Web server: GX real-time monitoring and setting
changes/operations can be performed with the
Web browser.
The screen layout can be determined
independently of the screen of the GX main unit.
SNTP client: Inquires the time to the SNTP
server and sets the GX.
SNTP server: Outputs the GX time.
Time resolution: 5 ms
DHCP client: Automatically obtain the network
address settings from the DHCP server.
Modbus client: Reads data from another device
and writes to the registers.
Modbus server: Loads measurement and math
channel data
Loads and writes communication channel data
Some control commands such as memory start
Modbus client* register access limitations
*: Required /MC option
Setting/Measurement server: Operate, set, and
output data of the GX using a dedicated protocol.
Batch Function
Function: Data management using batch names.
Enter text elds and batch comments in the data
le.
Batch name: Added to the le name of the
display data and event data.
Structure: Batch number (up to 32 characters) +
lot number (up to 8 digits)
Use/not use selectable for lot number, on/off
selectable for auto increment function.
Text eld: Adds text to the display data and event
data.
There are 24 available text elds.
Up to 20 title characters and 30 other characters
can be entered per eld.
Batch comment: Adds text to the display data
and event data.
3 comments (max. 50 characters) are available.
Printer Output Function
Snapshot Data can be printed out with any
LAN-connected printer supporting the HP-PCL5
language.
Other Functions
Buzzer: GX makes a buzzer sound at touch
screen operation, or when alarm occurs.
Backlight saver function: Dim or turn off the
LCD backlight if there is no key operation for a
specied time.
Favorite display: Register frequently used
displays to the Favorite and show them through
simple operation.
The main alarm is indicated using the MENU key
LED.
No alarm: Blue (same condition as power-on)