Manual

2
All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 04L51B01-01EN May. 7, 2013-00
Digital display
Displays measured values numerically
A DI input state can be displayed as an arbitrary
character string (0=Off/1=On, etc.)
Update rate: 0.5 s
Overview display
Display format: All channels (GX10: Max. 30,
GX20: Max. 100), each groups
Displays the measured values of all channels
and the alarm statuses
Alarm summary display
Displays a log of up to 1000 alarms
Specify an alarm with the cursor and jump to
the corresponding section on the historical trend
display.
Message summary display
Time and content of up to 500 messages
(including 50 add messages)
Specify a message with the cursor and jump to
the corresponding section on the historical trend
display.
Memory summary display
Displays the information (up to 500) of the data
in the memory
Specify a le with the cursor and jump to the
corresponding section on the historical trend
display.
Report display
Displays the report data residing in the internal
memory
For more details, see "MATHEMATICAL
FUNCTIONS WITH REPORT FUNCTION (/MT)."
Log display
Displays the event log, error log, communication
log, FTP log, Web log, e-mail log, SNTP log,
DHCP log, and Modbus log.
Multi-panel display
Divides the screen into two to six sections and
displays some different display formats.
Other displays
Network information display
System information display
System conguration display
Auto scroll ON/OFF:
The displayed groups can be automatically
switched at a specied interval.
The display switches in ascending group order.
Names of channels:
Channel number;
Analog input: 01 to 10
Digital input: 01 to 16
Digital output: 01 to 06
X X X X
Slot number; GX10: 0 to 2, GX20: 0 to 9
Main unit: 0
Tags:
Tag and Tag numbers can be displayed.
Tag number; Number of characters: Up to 16
Displayable characters: Alphanumeric characters
Tag numbers can be enabled or disabled.
Tag; Number of characters: Up to 32
Displayable characters: Alphanumeric characters
Message:
Write messages to the trend display.
Number of messages: 100
Number of characters: Up to 32
Write method: Write a preset message or write
an arbitrary message on the spot.
Write destination: Select only the displayed
group or all groups.
Auto message: Write a message when the GX
recovers from a power failure while memory
sampling is in progress.
Write a message when the trend interval is
switched during memory sampling.
Add message:
Write messages to the past data positions.
Message: The same as the “Message” item
above
Number of writable messages per le: 50
messages (including 10 freehand messages)
Freehand message:
Can be written by dedicated pen.
Number of writable messages per le: 50
messages (including 10 Add messages)
Data Saving Functions
Internal memory:
Temporarily saves various types of data.
Medium: Flash memory
File storage capacity: 500 MB
External storage medium:
Medium SD card (SD/SDHC) (up to 32 GB)
Format: FAT32 or FAT16
Data type:
Display data, Event data, Alarm summary data,
Manual sampled data, Screen image data, Setup
data, and Report data
Display data:
Target: Measurement (input/output module)/
math/communication channels, alarm summary,
message summary
Description: Maximum or minimum value per
recording interval
Recording intervals: Determined by the trend
interval
For GX20
Trend interval (div) Number of channels
5 s 100
10 s 200
15 s or longer
500
Note that the maximum number of channels is
xed at 100 in the GX10.
Data size;
Analog input data: 12 bytes/ch.
Digital I/O data: 4 bytes/ch.
Math channel data: 12 bytes/ch.
Communication channel data: 12 bytes/ch.
File size: Up to 18 MB
Number of les: Up to 500 (including event data)
Operation in the internal memory: FIFO (First In
First Out)
Data format: Binary or text
Recording: Records data at all times.
Display data le sample time
Measurement channel = 30. Math Channel = 0