Manual

1-111
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
Type
Set the action to execute when an event occurs.
When the Event Operation Mode Is Rising Edge or Falling Edge
Options Description
Recorded Starts or stops recording.
Computation Starts or stops computation (/MT option) or resets the computed values
of all math channels.
Switch the display rate Switches the trend interval and the secondary trend interval.
You can specify this setting when Trend rate switching is set to On.
Flag Sets the flag to 1 (On). (/MT option).
Manual sample Executes manual sampling.
Alarm ACK Clears the alarm output.
Snapshot Saves the screen image data.
Save display data Saves the display data being recorded to a file in the internal memory.
You can specify this when the GX/GP is configured to record display
data.
Save event data Saves the event data being recorded to a file in the internal memory.
You can specify this when the GX/GP is configured to event display
data.
Event trigger Applies a trigger that starts event data recording. You can specify this
when the GX/GP is configured to event display data.
Message Writes a message. Specify the message number and the message
write destination. Set the destination to all groups, or specify a write
destination group number. You can execute this while recording is in
progress.
Switch the display group Switches the display group in trend, digital, or bar graph display.
Specify the number of the group to display.
Reset the relative timer Resets a relative timer. The timer starts immediately.
Show the favorite display Switches to the specified favorite screen
Load settings Loads the setting parameter file in the root directory of the SD memory
card and configures the GX/GP accordingly. (See the explanation.)
Adjust the time Sets the clock to the nearest hour.
When the Event Operation Mode Is Rising/Falling Edge
Options Description
Recording start/stop Repeats recording start and stop on every event occurrence.
Computation start/stop Repeats computation (/MT option) start and stop on every event
occurrence.
Switch the display rate 1, 2 Switches the display rate on every event occurrence.
Flag On/Off Repeats the operation of setting the flag to 1 (On) and 0 (Off) on every
event occurrence.
Detail
Set the details when the action type is set to Recorded, Computation, or Message.
When Set to Recorded or Computation
Options Description
Start Starts recording or computation.
Stop Stops recording or computation.
Reset (Computation only) Resets computation.
When Set to Message
Options Description
All groups Writes the message to all groups.
Specified group Writes the message to the specified group. Set the destination by
specifying a group number.
1.14 Configuring the Event Action Function