Advanced Operation (Various settings and operation)
Using the Scaling Function
(Measuring a flow meter)
On channel 1 of slot 1 (0101), measure the input signal
ranging from 1 to 5 VDC as 0.0 to 100.0 m
3
/h.
Path MENU key > Browse tab > Setting >
Setting menu > AI channel settings > Range
1
2
3
4
5
7
8
9
10
11
6
1
Tap First-CH > 0101.
2
Check that Last-CH is 0101.
3
Tap Type > GS.
4
Tap Range > 1-5V.
5
Tap Calculation > Linear scaling.
6
Drag the screen up.
Show the setting parameters off the screen at the
bottom.
7
Tap Decimal place > 1.
8
Tap Scale Lower, and enter 0.0.
9
Tap Scale Upper, and enter 100.0.
10
Tap Unit, and enter m3/h.
11
Tap Save.
Operation complete
Registering and Deleting Favorite
Screens
You can register displays that you use frequently as
favorite screens and display them with easy operation.
You can register up to 20 displays.
Registering a Favorite Screen
1
Show the display that you want to register as a
favorite screen.
2
Press MENU.
The menu screen appears.
Add a favorite screen
Scroll
Close button
Favorite screen list
3
Tap Add favorite.
A conî‚¿rmation screen appears.
4
Tap Favorite name, and enter the name.
5
Tap OK.
The display is registered.
6
Tap the Close icon.
The screen closes.
Operation complete
Deleting a Favorite Screen
1
Press MENU.
2
Tap Universal tab > Remove favorite.
3
Select the screen to delete, and tap OK.
4
Tap the Close icon.
The screen closes.
Operation complete