Manual
26
IM 04L51B01-02EN
Advanced Operation (Various settings and operation)
Setting Measurement and Recording
Conditions
Configuring the type of data to record to display data, the
scan interval to 2 s, and the trend interval to 1 min.
Setting the Type of Data to Record
Path MENU key > Browse tab > Setting >
Setting menu > Recording Settings >
Basic settings
1
2
1
Tap File type > Display.
2
Tap Save.
You can set the file type to record only the data that
suits your purpose. For example, you can record
detailed data or record data only when alarms occur.
For details, see the User’s Manual (IM 04L51B01-
01EN).
Setting the Scan Interval
Path MENU key > Browse tab > Setting >
Setting menu > Measurement settings >
Scan interval
1
2
1
Tap Scan interval > 2s.
2
Tap Save.
Operation complete
Setting the Trend Interval
Path MENU key > Browse tab > Setting >
Setting menu > Display settings > Trend
interval
1
2
1
Tap Trend interval [/div] > 1 min.
2
Tap Save.
Operation complete
Setting Alarms
On channel 1 of slot 0, set the high limit alarm at the alarm
value of 150°C.
Path MENU key > Browse tab > Setting >
Setting menu > AI channel settings > Alarm
1
2
3
4
5
6
1
Tap First-CH > 0001.
2
Check that Last-CH is 0001.
3
Tap Level1 > On.
4
Tap Type > H.
5
Tap Value, and enter 150.0.
6
Tap Save.
Operation complete
This section explains how to change various settings.
Before you change settings, stop recording and computation.