Responded variations to event polls are shown in Table 25. When event data are read
with variation zero, DNP slave/server functions will respond with the same data type
to the default variation with putting timestamp information as needed.
Table 25. Responded variations to event poll
8
Object requested
variation
default
variation
Put time
stamp
Use relative
time
Responded
variation
Binary Input Event (2) 0 (zero) - No - 1
Yes No 2
Yes 3
none-0 - - - Requested
variation
Binary Output Event (11) 0 (zero) - No - 1
Yes - 2
none-0 - - - Requested
variation
Analog Input Event (32) 0 (zero) 1, 3 No - 1
Yes - 3
2, 4 No - 2
Yes - 4
5 No - 5
Yes - 7
6 No - 6
Yes - 8
none-0 - - - Requested
variation
Analog Output Event (42) 0 (zero) 1 No - 1
Yes - 3
2 No - 2
Yes - 4
3 No - 5
Yes - 7
4 No - 6
Yes - 8
none-0 - - - Requested
variation
'-' shows don't care
8
When objects are read via Class object, responded variation will be the same like as read
with variation 0.