User Manual
- 102/131 -
IM MW100-S16E-1
Ed01
2.5.14. DNP application service setting (WW)
This command is used to configure application service of DNP slave/server. For
implementing DNP communication functions, this command is added.
- Setting
WW p1, p2, p3, p4, p5, p6, p7, p8
32
p1 : Switch to permit unsolicited message (OFF, ON)
OFF : Not permit
ON : Permit
p2 : Switch to put timestamp to event data (OFF, ON)
OFF : Not put
ON : Put
p3 : Switch to use relative time as timestamp (OFF, ON)
OFF : Not use
ON : Use
p4 : Holding time of Select request [s] (1 to 60)
p5 : Event buffer size prepared to object (1 to 100)
p6 : Delay time from event happening to reporting [s] (0 to 60)
p7 : Maximum event count contained into a message (1 to 100)
p8 : Dead band of Analog Input, Analog Output objects (0 to 100)
- Query
WW ?
32
Unless DNP option is specified, command can't be used.