Owner's manual

2-40
IM MW100-17E
2.3 Binary Output
Note
In this section, CRLF means “carriage return/line feed.”
Output of the Latest Measured/Computed Data
Output using the FD1 command.
Format of Response to FD1 Command
'E' 'B' CR LF
Binary data
Data sum
Flag
Data length
Data block
Identifier=130
Latest measured/computed data
4 bytes
Identifier Header sum
Data Block Structure
8 bytes
Year
Channel number
Channel number
Channel number
Alarm status
Alarm status
Alarm status
Alarm 2
Bit 7 4 3 0 47 3 0
Alarm 1 Alarm 4 Alarm 3
Data value
Data value
Data value
Month Day Hours Minute Second (Reserved)
(Reserved)
2 bytes
Data Block Member Values
Member Name Value
Year
Month
Day
00 to 99 (70 to 99: 1970 to 1999, 00 to 69: 2000 to 2069)
1 to 12
1 to 31
Hour
Minute
Second
0 to 23
0 to 59
0 to 59
Channel number 1 to 60:
101 to 400:
Measurement Channel
MATH channels
Alarm value 0:
1:
2:
3:
4:
5:
6:
7:
8:
Alarm OFF
Upper limit alarm occurs
Lower limit alarm occurs
Differential upper limit alarm occurs
Differential lower limit alarm occurs
Upper limit on rate-of-change alarm occurs
Lower limit on rate-of-change alarm occurs
Delay upper limit alarm occurs
Delay lower limit alarm occurs
Data values –32767 to 65535
–9999999 to 99999999
Reserved Undefined
2.3 Binary Output