Owner's manual
1-38
IM MW100-17E
1.7 Control Commands
DS Operation Mode Switching
Setting
DSp1<terminator>
p1 Mode type
0 Measurement Mode
1 Setting Mode
Example Sets the mode to Setting mode.
DS1
Explanation The operation mode cannot be changed during
recording or computation operations.
EX Computation Start/Stop/Reset/
Clear
Setting
EXp1<terminator>
p1 Operation
0 Computation start
1 Computation stop
2 Reset computation
3 Clear computation
Example Starts computation.
EX0
Explanation
•
Y
ou can set this command on products with the
/M1 MA
TH function option, or when the pulse input
module is installed.
• Computation cannot be started or stopped during
recording.
• You cannot start computation if MATH is not turned
ON on at least one MA
TH channel using SO
command.
• Computation cannot be started if the MATH interval
is OFF, 10 ms, or 50 ms.
PS Recording Start/Stop
Setting
PSp1<terminator>
p1 Recording start/stop
0 Start
1 Stop
Example Starts recording.
PS0
Explanation • When recording is started, measured data is saved
to the CF card.
• If the allowed size of a created measured value file,
computed value file, or thinned value file is exceeded
due to the combination of the recording channel,
recording interval, and recording data length,
recording will not be started.
• If the thinning recording interval is shorter than the
measurement or MA
TH interval, recording will not
start.
MV Setting File Save/Write
Setting
MVp1,p2<terminator>
p1 Operation
0 Save settings file
1 Load settings file
p2 File name (up to 8 characters)
Example Loads settings file “SETFILE1.”
MV1,SETFILE1
Explanation • Specify the file name without the extension.
• For the characters that can be used for file names,
see “File Name and Foldr Name String” in section
1.3.
MQ Measured, Computed, and
Thinned File Division
Setting
MQp1<terminator>
p1 Operation
SAVE_M Execute division and saving
of measurement / computation
file
SAVE_T Execute division and saving
of thinned file
Example
Divides measurement files.
MQSAVE_M
Explanation After dividing a file, the next file division is enabled 10
minutes later
.
MS Message Writing
Setting
MSp1<terminator>
p1 Message Number (0 to 5)
Example Write message number 1.
MS1
MP Execution of Manual Sample
Setting
MPp1<terminator>
p1 Operation
SAMPLE Perform manual sample
DIVIDE Divide manual sample file
Example Perform a manual sample.
MPSAMPLE
Explanation A new manual sample cannot be performed while a
manual sample file is being written (approximately 2
seconds).
KI Main Unit Key Operation
Setting
KIp1<terminator>
p1 Key type
START1 START key
START2 START key (equivalent to
holding down for 2 sec)
STOP1 STOP key
1.7 Control Commands