Owner's manual

1-7
IM MW100-17E
Commands
1
2
3
AppApp
Index
Contact
Input Type
Contact
String
DI
Measuring Range
Level
Contact
String
LEVEL
CONTACT
Setting Range for Lower/Upper
Limit of Span
0 or 1 (0 for less than 24 V,
1 for 24 V or more)
0 or 1 (0 for contact OFF, 1
for contact ON)
Difference Computation
–1, 0, 1
–1, 0, 1
Thermocouple
RTD
Input Type
RTD
String
RTD
Measuring Range
Pt100 [1]
[2]
JPt100 [1]
[2]
Pt100 [1]
(high
[2] resolution)
JPt100 [1]
(high [2]
resolution)
Ni100 SAMA
Ni100 DIN
Ni120
Pt50
Cu10 GE
Cu10 L&N
Cu10 WEED
Cu10 BAILEY
J263B
Cu10 at 20°C
a=0.00392
Cu10 at 20°C
a=0.00393
Cu25 at 0°C
a=0.00425
String
Pt100-1
Pt100-2
JPt100-1
JPt100-2
Pt100-1H
Pt100-2H
JPt100-1H
JPt100-2H
Ni100SAMA
Ni100DIN
Ni120
Pt50
Cu10GE
Cu10LN
Cu10WEED
Cu10BAILEY
J263B
Cu10a392
Cu10a393
Cu25
Setting Range for Lower/Upper Limit
of Span
–200.0 to 600.0 °C
–200.0 to 250.0 °C
–200.0 to 550.0 °C
–200.0 to 250.0 °C
–140.00 to 150.00 °C
–140.00 to 150.00 °C
–200.0 to 250.0 °C
–60.0 to 180.0 °C
–70.0 to 200.0 °C
–200.0 to 550.0 °C
–200.0 to 300.0 °C
–200.0 to 300.0 °C
–200.0 to 300.0 °C
–200.0 to 300.0 °C
0.0 to 300.0 K
–200.0 to 300.0 °C
–200.0 to 300.0 °C
–200.0 to 300.0 °C
Differential Computation
±800.0 °C
±450.0 °C
±750.0 °C
±450.0 °C
±290.00 °C
±290.00 °C
±450.0 °C
±240.0 °C
±270.0 °C
±750.0 °C
±500.0 °C
±500.0 °C
±500.0 °C
±500.0 °C
±300.0 K
±500.0 °C
±500.0 °C
±500.0 °C
The number in brackets for the setting range is the RTD measurement current (mA). If no number is
given, 1 mA, 2 mA, or both are supported.
1.3 Parameters