Display Possible Problem Corrective Action
E314 File is write-protected. Check write permissions.
E315 No such le or directory. Check the les and folders. *
E316 Number of les exceeds the upper limit. Delete unneeded les to reduce the number of les.
E317 Invalid le or directory name. Check the les and folders. *
E318 Unknown le type. Check the les.
E319 Same name of le or directory already exists. Check the les and folders. *
E320 Invalid le or directory operation. Check the les and folders. *
E321 File is in use. Wait until access is nished.
E331 Setting le not found. Check the name of the setting le.
E332 Setting le is broken. Could not load setting le because it is corrupted.
E341 FIFO buffer overow. You must reduce the time required to store les.
Delete unneeded les to free up space.
E342 Data to be saved to le not found. Check the settings.
E343
Power failed while opening le. Files may have been damaged.
Take appropriate action for power failure.
E344 Some or all data prior to power outage could Do not change the CF card during a power failure.
not be recovered.
E345 Could not restart recording after recovery from Perform the record start operation.
power failure.
E346 Recording could not be started due to power Perform the re-recording start operation.
outage. Take approp
riate action for power failure.
* May occur in the MW100 internal processing. (during an abnormality)
Communication Command Error
The code is divided into two parts which are displayed alternately on the 7-segment LED;
in the first part, the letter E appears in the left digit with the hundreds digit of the error
code to the right, and the second part consists of the last two digits of the error code.
Display Possible Problem Corrective Action
E401 Command string too long. Keep the command within 2047 characters from rst character to
terminator.
E402 Too many commands enumerated.
Set the number of enumerated commands within 99.
E403 Invalid type of commands enumerated. Send the commands without enumerating them.
E404 Invalid command. Conrm the command name.
E405 Not allowed to execute this command. Login at a level that allows execution of this command.
E406 Cannot execute due to different operation mode. Switch to a mode that allows execution of this command.
E407 Invalid number of parameters. Check the number of parameters.
E408 Parameter string too long. Keep the length of individual parameters within 512 Bytes.
E411 Daylight saving time function not available. Check the daylight saving time settings.
Not available with the current model.
E412 Temperature unit selection not available. Not available
with the current model.
E413 MATH option not available. Not available with the current model.
E414 Serial communication interface option not Not available with the current model.
available.
E415 Report option not available.
Not available with the current model.
Appendix 7 Error Display on the 7-Segment LED and Corrective Actions