2.4 Connecting Signal Wires
CAUTION
If a large pulling force is applied to the input/output signal wires connected to the
MW100, the terminal or signal wire may break. To prevent this from happening,
secure all the wiring cables to the installation panel.
Do not apply a voltage exceeding the value indicated below to the input
terminals of the universal input modules. Doing so can damage the modules.
• Maximum input voltage
Voltage range of 1 VDC or less, TC, R
TD, and DI (contact): ± 10 VDC
Voltage range of 2 VDC or more, and DI (LEVEL): ± 120 VDC
• Maximum common mode voltage
Between channels: 250 VACrms (50/60 Hz) (-H04)
120 VACrms (50/60 Hz) (-M10)
Input to ground: 600 VACrms (50/60 Hz)
Do not apply a voltage exceeding the values indicated below to the input
terminals of the DCV/TC/DI input module. Doing so can damage the module.
• Maximum input voltage
Voltage range of 1 VDC or less, TC, and DI (contact): ± 10 VDC
Voltage range of 2 VDC or more, and DI (LEVEL): ± 120 VDC
• Maximum common mode voltage
Between channels: 120 VACrms (50/60 Hz)
Input to ground: 600 VACrms (50/60 Hz)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the 4-Wire RTD resistance input module. Doing so can damage the
module.
• Maximum input voltage
Voltage range of 1 VDC or less, RTD, resistance, and DI (contact): ± 10 VDC
Voltage range of 2 VDC or more, and DI (LEVEL): ± 120 VDC
• Maximum common mode voltage
Between channels: 120 VACrms (50/60 Hz)
Input to ground: 600 VACrms (50/60 Hz)
Wiring of the Strain Input Module (-NDI)
When connecting a bridge head, in order that the empty weight of the cable
does not exceed 5 kg, ensure that the cable does not hang down more than 1.5
m (the distance to the floor). If the cable hangs longer than 1.5 m, secure the
cable to the installation panel or some other location.
Do not apply a voltage exceeding the value indicated below to the input
terminals of the strain input modules. Doing so can damage the modules.
• Maximum input voltage: ± 10 VDC
• Maximum common mode voltage
Between channels: 30 VACrms (50/60 Hz)
Input to ground: 250 V
ACrms (-B12, -B35), 30 VACrms (-NDI) (50/60 Hz)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the pulse input module. Doing so can damage the module.
• Maximum input voltage: ± 10 VDC
• Maximum common mode voltage
Input to ground: 250 VACrms (50/60 Hz)
When using the pulse input module with contact input, the measured signal
becomes easily affected by wiring impedance at high speed. The cable should
be approximately 25 m or less when the pulse width is 0.05 ms, or 500 m or less
at 0.5 ms. The wiring impedance varies depending on the such things as the
cable length, type, and wiring conditions.