Instruction Manual
1-57
IM MW100-01E
Explanation of Functions
1
2
3
4
5
App
Index
Output Operation during an Abnormality and after Recovery from the Abnormality
Output Operation during an Abnormality (by Module)
Abnormal Module Display Status Output Operation
Main module b
c
*1
System errors Operation when power is turned ON
bF Dip switches
F0 ROM error
F1 SRAM error
F2 EEPROM error
F3 Battery error
F4 Ethernet error
Output modules U0 Range information error Operation when power is turned ON or
U1 Calibration value error
when output value uncertain
U2 Error during calibration Internal communication error occurred,
resulting in an error recovery event. If
the error recovery time is 10 s or more,
output is performed per the operation for
U3 Error in writing the
error occurrence, and then output is
calibration value.
executed per the operation for power ON.
U4 Unusable modules Operation when power is turned ON or
when output value uncertain
Input modules U0
Range information error Operation when errors occur (transmission
U1 Calibration value error
between units output only, since the
U4 Unusable modules
transmission source input channel is
illegal
*2
)
*1 The number corresponding to the error is shown in the
c
.
*2 Illegal occurs when a module is removed, when a module recognition fails, or when a module
malfunctions.
1.13 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output