Instruction Manual

App-11
IM MW100-01E
Appendix
1
2
3
4
5
App
Index
Appendix 4 E-Mail Format
In the explanations that follow,
CRLF
means “carriage return/line feed.”
A user-defined character string can be attached to the subject of each mail.
Alarm Notification E-mail Format
Subject
Subject: [Alarm Summary]
Syntax
CRLF
Alarm_SummaryCRLF
DATE_yy/mo/ddCRLF
TIME_hh:mi:ssCRLF
CRLF
<Alarm Summary>CRLF
cc____lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm_lq_aaaCRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
<CH_Data>CRLF
ccc*ddddddd_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
mmmm*eeeeeeeee_[uuuuuu]CRLF
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
CRLF
ENDCRLF
CRLF
yy
Year (
00
to
99
)
mo
Month (
01
to
12
)
dd
Day (
01
to
31
)
hh
Hour (
00
to
23
)
mi
Minute (
00
to
59
)
ss
Seconds (
00
to
59
)
*
Tab
ccc
Measurement ch no. (
001
to
060
, SKIP channels not output)
mmmm
MATH ch no. (
A001
to
A300
, OFF channels not output)
l
Alarm level (
1
to
4
)
q
Alarm type (
H
,
L
,
h
,
l
,
R
,
r
,
T
,
t
)
H
(upper limit alarm),
L
(lower limit alarm),
h
(differential upper limit
alarm),
l
(differential lower limit alarm),
R
(upper limit on rate-of-
change alarm),
r
(lower limit on rate-of-change alarm),
T
(delay
upper limit alarm),
t
(delay lower limit alarm)
aaa
Alarm status (
off
,
on
)
ddddddd
Measured data (measurement channel, includes decimal point and
minus sign, all space filled in to the left when 6 characters or fewer)
eeeeeeeee
Computed data (MATH channel, includes decimal point and minus