User's Manual 3 Series MODBUS Communication Type (Option /MB1) Coriolis Mass Flow and Density Meter Integral Type RCCT3 Remote Type RCCF31 + RCCS3 Remote Type RCCR31 + RCCS3 IM 01R04B08-00E-E, additional manual to IM 01R04B04-00x-E Rota Yokogawa GmbH & Co. KG Rheinstr.
Blank Page
i Contents 1. INTRODUCTION....................................................................................1-1 1.1 Using the Coriolis Flowmeter Safely...............................................................1-2 1.2 Warranty..............................................................................................................1-3 1.3 Instruction according EMC...............................................................................1-3 1.4 ATEX Documentation....................
ii 9. MODBUS COMMUNICATION TOOL.....................................................9-1 9.1 Preconditions....................................................................................................9-1 9.2 Installation and start.........................................................................................9-1 9.3 Using the Modbus Communication Tool........................................................9-1 10. GENERAL SPECIFICATIONS..............................................
<1. INTRODUCTION> 1-1 1. INTRODUCTION This instrument has been adjusted at the factory before shipment. To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it. NOTE This manual describes the hardware and software configurations of the Rotamass Coriolis Massflowmeter. Regarding This User's Manual • This manual should be provided to the end user. • Before use, read this manual thoroughly to comprehend its contents.
1-2 <1. INTRODUCTION> Protective grounding terminal Functional grounding terminal (This terminal should not be used as a protective grounding terminal.) Alternating current Direct current 1.1 Using the Coriolis Flowmeter Safely WARNING (1) Installation • Installation of the Coriolis flowmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation. • The Coriolis flowmeter is a heavy instrument.
<1. INTRODUCTION> 1.2 Warranty • The warranty terms of this instrument that are guaranteed are described in the quotation. We will make any repairs that may become necessary during the guaranteed term free of charge. • Please contact our sales office if this instrument requires repair. • If the instrument is faulty, contact us with complete details about the problem and the length of time it has been faulty, and state the model and serial number.
1-4 <1. INTRODUCTION> 1.4 ATEX Documentation This is only applicable to the countries in European Union. GB SK CZ DK I LT E LV EST NL PL SF SLO P H F BG D RO S M GR IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
1-5 <1. INTRODUCTION> 1.5 Disposal, Cleaning and Return For safe use WARNING If the process fluid is harmful to personnel, handle the instrument carefully even after it has been removed from the process line for maintenance or other purposes. Exercise extreme care to prevent the fluid from coming into contact with human skin and to avoid inhaling any residual gas.
1-6 <1. INTRODUCTION> ROTA YOKOGAWA GmbH & Co. KG Service & Repair Department Rheinstraße 8; D - 79664 Wehr Phone no.: +49 (0)7761-567-190 Fax no.: +49 (0)7761-567-285 e-Mail: services.flow@de.yokogawa.com Declaration of Decontamination Legal regulations for the safety of our employees and operating equipment determine that we need the declaration of decontamination before your order can be handled.
<2. AMPLIFIER FOR MODBUS COMMUNICATION > 2-1 2. AMPLIFIER FOR MODBUS COMMUNICATION Refer to IM 01R04B04-00E for the details of the amplifier. This section encompasses topics applicable to only the Modbus communication type. (1) The Modbus communication type has only one current output (Iout1). (2) For the Modbus communication type intrinsically safe outputs are not available. (3) Concurrent write access via Modbus and HART should be avoided.
2-2 <2. AMPLIFIER FOR MODBUS COMMUNICATION > Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
<3. ABOUT MODBUS> 3-1 3. ABOUT MODBUS 3.1 Outline MODBUS is a bi-directional digital communication protocol also for field devices, which offers an advancement in communication speed and is widely employed by numerous field devices. The MODBUS communication type of the Rotamass employs the specification standardized by the MODBUS Organization, and provides interoperability with devices produced by other manufacturers.
3-2 <3. ABOUT MODBUS>> Figure 3.1 Device Connection Before using a MODBUS configuration tool other than the existing host, confirm it does not affect the loop functionality in which all devices are already installed in operation. Disconnect the relevant control loop from the bus if necessary. IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
<4. GETTING STARTED> 4-1 4. GETTING STARTED MODBUS is digital communication protocol and differs in operation from 4 to 20 mA transmission and the HART communication. It is recommended that users use MODBUS devices in accordance with the procedures described in this section. The procedures assume that MODBUS devices will be set up on a bench of an instrument shop. 4.1 Wiring in ROTAMASS 3 Terminal Box Figure 4.
4-2 <4. GETTING STARTED> 4.2 Communication Setting To activate MODBUS, the following settings are required. They are located in the MODBUS Communication menu in Detailed Setup. IMPORTANT Connecting the ROTAMASS MODBUS communication tool to a bus with its existing host may cause communication data scrambles resulting in a functional disorder or a system failure. IMPORTANT Do not turn off the power supply immediately after setting.
<4. GETTING STARTED> 4-3 4.3 Reading and Writing Values Unlike other communication protocols MODBUS does not use standardized device description files but store data and parameters in registers. An overview of the Modbus registers of ROTAMASS can be found in chapter 7. For configuration the ROTAMASS MODBUS communication tool is available from Yokogawa which can address parameters of ROTAMASS which are mapped onto MODBUS. The tool can be found on the DVD which is attached to each device.
4-4 <4. GETTING STARTED> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
<5. OPERATION OF ROTAMASS 3 SERIES MODBUS COMMUNICATION TYPE> 5-1 5. OPERATION OF ROTAMASS 3 SERIES MODBUS COMMUNICATION TYPE 5.1 Operation via display For general information regarding the operation via display refer to the instruction manual of the standard type IM 01R04B04-00E-E. For the Modbus communication type the operation via display is basically the same.
5-2 <5. OPERATION OF ROTAMASS 3 SERIES MODBUS COMMUNICATION TYPE> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
6-1 <6. PARAMETER> 6. PARAMETER Parameters in light grey are not mapped onto Modbus for ROTAMASS with option /MB1. For configuration they can still be accessed via HART communication on analog output 1 or via the display menu. Parameters in dark grey are not available. The default value of selection items is typed in bold letters.
6-2 Diag/Service <6.
6-3 <6.
6-4 Basic Setup <6.
6-5 <6. PARAMETER> Basic Setup Display contrast -5 Sel -4 -3 -2 -1 0 +1 +2 +3 +4 +5 Mass flow Mass flow unit g/s Sel g/min g/h kg/s kg/min kg/h kg/d t/min t/h t/d lb/s lb/min lb/h lb/d Density Mass flow LRV R/W Mass flow URV R/W Mass flow damping R/W Density unit g/ml Sel kg/l kg/m³ lb/gal lb/Cuft g/cm³ g/l °Bé hv °Bé lt °API Density LRV R/W Density URV R/W Density damping R/W All Rights Reserved.
6-6 Basic Setup <6.
6-7 <6. PARAMETER> Basic Setup Pulse 1 unit Hz Sel g/P kg/P t/P lb/P cm³/P l/P m³/P gal/P kgal/P Cuft/P bbl/P Impgal/P klmpgal/P I(N)/P m³(N)/P SI/P Scuft/P Sm³/P Pulse 1 rate SO 1 function R/W No Function Sel Flow direction Total switch Mass flow alm 1 Mass flow alm 2 Mass flow alm 1+2 Vol flow alm 1 Vol flow alm 2 Vol flow alm 1+2 Density alm 1 Density alm 2 Density alm 1+2 Temp alm 1 Temp alm 2 Temp alm 1+2 Concentr. meas alm 1 Concentr. meas alm 2 Concentr.
6-8 Basic Setup <6.
6-9 <6. PARAMETER> Basic Setup SO 2 function No Function Sel Flow direction Total switch Mass flow alm 1 Mass flow alm 2 Mass flow alm 1+2 Vol flow alm 1 Vol flow alm 2 Vol flow alm 1+2 Density alm 1 Density alm 2 Density alm 1+2 Temp alm 1 Temp alm 2 Temp alm 1+2 Concentr. meas alm 1 Concentr. meas alm 2 Concentr.
6-10 Basic Setup <6. PARAMETER> Total flex unit g Sel kg t lb cm³ l m³ gal kgal Cuft bbl Impgal Klmpgal I(N) m³(N) SI Scuft MMscuft Sm³ Total mass unit g Sel kg t lb Total volume unit cm³ Sel l m³ gal kgal Cuft bbl Impgal Klmpgal I(N) m³(N) SI Scuft MMscuft Sm³ IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
6-11 <6.
6-12 Detailed Setup <6.
6-13 <6. PARAMETER> Detailed Setup Disp select 4 Mass flow Sel Volume flow Density Temperature Concentration meas Net flow F-Total flex R-Total flex D-Total flex F-Total mass R-Total mass D-Total mass F-Total volume R-Total volume D-Total volume F-Total net R-Total net D-Total net F-Total energy Velocity Drive gain None Display contrast -5 Sel -4 -3 -2 -1 0 +1 +2 +3 +4 +5 Disp period 0.5s Sel 1.0s 2.0s Language English Sel German French Russian All Rights Reserved.
6-14 <6. PARAMETER> Detailed Setup Sensor model RCCS30 Sel RCCS31 RCCS32 RCCS33 RCCS34 RCCS36 RCCS38 RCCS39 RCCS39/IR RCCS39/XR RCCS30/LR Sensor constants Mass flow Density Config fld variables IM 01R04B08-00E-E Flow direction 1st edition February 15, 2012 -00 SK20 R/W SKT R/W SKTK R/W RV R/W Qnom R SKP R/W SKPT R/W KD R/W fl20 R/W FTC1 R/W FTCK R/W FPC R/W FPTC R/W FQC1 R/W FQC2 R/W Forward Reverse Sel All Rights Reserved.
6-15 <6. PARAMETER> Detailed Setup Mass flow Mass flow unit g/s Sel g/min g/h kg/s kg/min kg/h kg/d t/min t/h t/d lb/s lb/min lb/h lb/d Mass flow format xxxxxxx Sel xxxxx.X xxxx.XX xxx.XXX xx.XXXX x.
6-16 Detailed Setup <6. PARAMETER> Volume flow Vol flow unit cm³/s Sel cm³/min cm³/h l/s l/min l/h l/d m³/s m³/min m³/h m³/d gal/s gal/min gal/h gal/d Cuft/s Cuft/min Cuft/h Cuft/d bbl/s bbl/min bbl/h bbl/d Impgal/s Impgal/min Impgal/h Impgal/d I(N)/s I(N)/min I(N)/h l(N)/d m³(N)/s m³(N)/min m³(N)/h m³(N)/d SI/s SI/min SI/h Sl/d Scuft/s Scuft/min Scuft/h Scuft/d Sm³/s Sm³/min Sm³/h Sm³/d IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
6-17 <6. PARAMETER> Detailed Setup Vol flow format xxxxxxx Sel xxxxx.X xxxx.XX xxx.XXX xx.XXXX x.XXXXX Vol flow LRV R/W Vol flow URV R/W Vol flow damping R/W Vol flow lowcut R/W Vol flow alm 1 sel No function Sel More than Less than Vol flow alm 1 crit Vol flow alm 2 sel R/W No function Sel More than Less than Vol flow alm 2 crit Density Density unit R/W g/ml Sel kg/l kg/m³ lb/gal lb/Cuft g/cm³ g/l °Bé hv °Bé lt °API Density format xxxxxxx Sel xxxxx.X xxxx.XX xxx.XXX xx.XXXX x.
6-18 <6. PARAMETER> Detailed Setup Density lowcut R/W No function Density alm 1 sel Sel More than Less than Density alm 1 crit R/W No function Density alm 2 sel Sel More than Less than Density alm 2 crit R/W Inhibit Density fix val sel Sel Enable Reference density R/W Density offset R/W bar Pressure Unit Sel psi MPa Pressure Temperature R/W degC Temperature unit Sel degF K Temperature format xxxxxxx Sel xxxxx.X xxxx.XX xxx.XXX xx.XXXX x.
6-19 <6. PARAMETER> Detailed Setup No function Temp alm 2 sel Sel More than Less than Temp alm 2 crit R/W Inhibit Temp fix val select Sel Enable Velocity unit Temp fixed value R/W Temp gain R/W m/s Sel ft/s Config Output/Input Analog output 1 Mass flow Analog 1 select Sel Volume flow Density Temperature Concentration meas Net flow None Analog 1 alarm Out <2.4 mA Sel <3.6 mA <4.0 mA >21.0 mA >21.
6-20 <6. PARAMETER> Detailed Setup Pulse 1 unit Hz Sel g/P kg/P t/P lb/P cm³/P l/P m³/P gal/P kgal/P Cuft/P bbl/P lmpgal/P klmpgal/P I(N)/P m³(N)/P SI/P Scuft/P Sm³/P Pulse 1 rate R/W Pulse 1 active mode On Active Sel Off Active Pulse 1 width 0.05ms Sel 0.1ms 0.5ms 1ms 5ms 10ms 50ms 100ms 50ms 1000ms Pulse 1 at alarm 0P/0Hz Sel Measured value Hold IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
6-21 <6. PARAMETER> Detailed Setup No Function SO 1 function Sel Flow direction Total switch Mass flow alm 1 Mass flow alm 2 Mass flow alm 1+2 Vol flow alm 1 Vol flow alm 2 Vol flow alm 1+2 Density alm 1 Density alm 2 Density alm 1+2 Temp alm 1 Temp alm 2 Temp alm 1+2 Concentr. meas alm 1 Concentr. meas alm 2 Concentr.
6-22 <6. PARAMETER> Detailed Setup Hz Pulse 2 unit Sel g/P kg/P t/P lb/P cm³/P l/P m³/P gal/P kgal/P Cuft/P bbl/P lmpgal/P klmpgal/P I(N)/P m³(N)/P SI/P Scuft/P Sm³/P Pulse 2 rate R/W Pulse 2 active mode On Active Sel Off Active Pulse 2 width 0.05ms Sel 0.1ms 0.5ms 1ms 5ms 10ms 50ms 100ms 50ms 1000ms Pulse 2 at alarm 0P/0Hz Sel Measured value Hold IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
6-23 <6. PARAMETER> Detailed Setup SO2 function No Function Sel Flow direction Total switch Mass flow alm 1 Mass flow alm 2 Mass flow alm 1+2 Vol flow alm 1 Vol flow alm 2 Vol flow alm 1+2 Density alm 1 Density alm 2 Density alm 1+2 Temp alm 1 Temp alm 2 Temp alm 1+2 Concentr. meas alm 1 Concentr. meas alm 2 Concentr.
6-24 <6.
6-25 <6.
6-26 Detailed Setup <6.
6-27 <6. PARAMETER> Detailed Setup Total reset Not Execute Reset flex totals Exe Reset mass totals Exe Reset volume totals Exe Reset net totals Exe Reset all totals Exe HART communication Poll addr R/W Num req pream R/W Num resp pream R/W Master reset Exe Modbus communication Modbus init Concentration setup Concentration meas R/W Device address R/W Baud rate R/W Data format R/W Modbus mode R/W Reference Temperature R/W Ref. density carrier R/W Temp. coeff.
6-28 <6. PARAMETER> Detailed Setup Concentr.meas LRV R/W Concentr. meas URV R/W Concentr. meas Damp R/W Concentr.
6-29 <6. PARAMETER> gal/min gal/h gal/d Cuft/s Cuft/min Cuft/h Cuft/d bbl/s bbl/min bbl/h Detailed Setup bbl/d Impgal/s Impgal/min Impgal/h Impgal/d Net flow format xxxxxxx Sel xxxxx.X xxxx.XX xxx.XXX xx.XXXX x.
6-30 <6.
6-31 <6. PARAMETER> Device id R Universal rev R Fld dev rev R Software rev R Hardware rev R Detailed Setup All Rights Reserved.
6-32 <6. PARAMETER> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
7-1 <7. MODBUS REGISTERS> 7. MODBUS REGISTERS All available parameters are assigned to holding registers wherein the measurement values and units are assigned to input registers on Modbus. A list of all available parameters and registers for Modbus communication option /MB1 can be found in the table below. The table contains also the selection values which can be written to selection parameters. Holding registers start at 40000h, input registers at 30000h.
7-2 Parameter Mass flow unit <7. MODBUS REGISTERS> Data range Selection value g/s 70 g/min 71 g/h 72 kg/s 73 kg/min 74 kg/h 75 kg/d 76 t/min 77 t/h 78 t/d 79 lb/s 80 lb/min 81 lb/h 82 lb/d 83 Read Unit Write Execute Holding Register Address (decimal) - R/W 1072 1088 Mass flow LRV -Qmax to Qmax - Mass flow unit R/W Mass flow URV -Qmax to Qmax - Mass flow unit R/W 1104 Mass flow damping 0 to 200 - Sec.
7-3 <7.
7-4 <7.
7-5 <7. MODBUS REGISTERS> Parameter Data range Temp gain 0.8 to 1.
7-6 Parameter Total net unit Total switch select Total limit switch Total unit energy Modbus init Device address IM 01R04B08-00E-E <7.
7-7 <7.
7-8 <7.
7-9 <7. MODBUS REGISTERS> Selection value Parameter Data range Net flow lowcut 0 to 10% of Qmax - No function 0 More than 1 Less than 2 Net flow alm 1 sel Net flow alm 1 crit Sensor model Master reset Drive Gain -110% to 110% of URV - RCCS30 0 RCCS31 1 RCCS32 2 RCCS33 3 RCCS34 4 RCCS36 5 RCCS38 6 RCCS39 7 RCCS39/IR 8 RCCS39/XR 9 RCCS30/LR 10 Not Execute - Execute - - - All Rights Reserved.
7-10 <7. MODBUS REGISTERS> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
8-1 <8. TECHNICAL DETAILS OF MODBUS COMMUNICATION> 8. TECHNICAL DETAILS OF MODBUS COMMUNICATION 8.1 Range check According to the Modbus specification error bit and exception codes are only defined for physical transmission errors. Therefore there is no possibility to signal logical errors like violation of data ranges or invalid selections at the time when a register is being written. ROTAMASS 3 Series Modbus communication type will check all values written via Modbus.
8-2 <8. TECHNICAL DETAILS OF MODBUS COMMUNICATION> 8.3 Transmission of status information Modbus protocol is designed to reduce overhead. Therefore there is no continuous transmission of status information. ROTAMASS 3 Series Modbus communication type provides three holding and input registers to read the current status of error (HR 896, IR 42), alarm (HR 912, IR 43) and warning (HR 928, IR 44) messages at the time when the registers are being read.
<8. TECHNICAL DETAILS OF MODBUS COMMUNICATION> 8-3 The following table shows possible countermeasures : Alarm (A); Warning (W) Error (E) A-01 A-02 A-03 A-04 A-05 A-06 A-07 A-08 A-09 A-10 A-11 A-12 MF 1 criteria MF 2 criteria VF 1 criteria VF 2 criteria Dens. 1 criteria Dens. 2 criteria Temp. 1 criteria Temp. 2 criteria Conc. 1 criteria Conc. 2 criteria Netflow 1 crit. Netflow 2 crit.
8-4 <8. TECHNICAL DETAILS OF MODBUS COMMUNICATION> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
<9. MODBUS COMMUNICATION TOOL> 9-1 9. MODBUS COMMUNICATION TOOL 9.1 Preconditions The Modbus Communication Tool was designed to support the parameters and values of the ROTAMASS 3 Series Modbus communication type which are available via Modbus. The Modbus Communication Tool supports the same communication settings as ROTAMASS.
9-2 <9. MODBUS COMMUNICATION TOOL> Adjustment of the communication settings Reading of measurement values IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
<9. MODBUS COMMUNICATION TOOL> 9-3 Configuration All Rights Reserved.
9-4 <9. MODBUS COMMUNICATION TOOL> Blank Page IM 01R04B08-00E-E 1st edition February 15, 2012 -00 All Rights Reserved.
10-1 <10. GENERAL SPECIFICATIONS> 10. GENERAL SPECIFICATIONS For specifications other than below, refer to IM 01R04B04-00E.
10-2 <10.
<10. GENERAL SPECIFICATIONS> 10-3 Remote field-mount Converter RCCF31, Model, Suffix and Option Code Model Suffix Code Option Description Code RCCF31 Power supply Restrictions Remote field-mount converter to be connected to RCCS3; when ordered without detector combination option /NC must be selected -A -D Indicator direction 90 - 264 V AC 24 V DC H2 N0 Cable conduit connection With indicator Without indicator M A Hazardous Area Approvals 1) M20 x 1.
10-4 <10.
Blank Page All Rights Reserved.
YOKOGAWA ELECTRIC CORPORATION World Headquarters 9-32, Nakacho 2-chome, Musashino-shi Tokyo 180-8750 Japan www.yokogawa.com YOKOGAWA ELECTRIC ASIA Pte. LTD. 5 Bedok South Road Singapore 469270 Singapore www.yokogawa.com/sg YOKOGAWA CORPORATION OF AMERICA 2 Dart Road Newnan GA 30265 USA www.yokogawa.com/us YOKOGAWA CHINA CO. LTD. 3F Tower D Cartelo Crocodile Building No.568 West Tianshan Road Changing District Shanghai, China www.yokogawa.com/cn Euroweg 2 3825 HD AMERSFOORT The Netherlands www.yokogawa.