Instruction Manual
7-11
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
Pulse 1 rate Decimal
0 to 11000 Unit/ P
0 to 10000 Hz
0 to 5
0
Pulse 1 unit R/W X 1 kg/P
Pulse 1 active mode Select On Active - - R/W X On Active
Off Active
Pulse 1 width Select 0.05ms - - R/W X 1ms
0.1ms
0.5ms
1ms
5ms
10ms
50ms
100ms
500ms
1000ms
Pulse 1 at alarm Select 0P/0Hz - - R/W X 0P/Hz
Measured Value
Hold
SO 1 function Select No function - - R/W X No function
Flow-Direction
Total switch
Mass ow alm 1
Mass ow alm 2
Mass ow alm 1+2
Vol ow alm 1
Vol ow alm 2
Vol ow alm 1+2
Density alm 1
Density alm 2
Density alm 1+2
Temp alm 1
Temp alm 2
Temp alm 1+2
Concentr. meas alm 1
Concentr. meas alm 2
Concentr. meas alm 1+2
Net ow alm 1
Net ow alm 2
Net ow alm 1+2
Slug alarm
Empty alarm
Corrosion alarm
All alarms
All errors
All alarms & errors
SO 1 active mode Select On Active - - R/W X On Active
Off Active
Pulse/Stat 2 select Select Pulse - - R/W X Status out
Status out
No function