Instruction Manual
6-6
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
The HART menu in chapter 7.4 shows the conguration of the online menu, which is needed
for the opera-
tion with HART communicator. Select ´Device Setup´ to call up the desired item as follows:
There are two choices to select the desired menu item:
1. Use the ↓ or ↑ key to select the desired item, and then press the → key.
2. Press the number key displayed for the desired item.
To return to the previous display, press the ← key
Entering, setting and sending data:
The data, which is input with the keys is set in the HART-communicator by pressing . Then, by
pressing , the data is sent to RCCT_F3. Note that the data is not sent to ROTAMASS if is not
pressed. All the data set with the HART-communicator is held in memory unless power is turned off, so all
data can be send to RCCT_F3 in one lot.
IMPORTANT
Parameter setting on the display with the infrared keys is prohibited during HART communication.
IMPORTANT
Do not turn power off just after HART-Communicator settings (sending) have been made. If ROTAMASS
is turned off less than 30 seconds after parameters have been set, the set data will not be stored and the
data returns to previous settings.
When over run error, framing error, parity error or buffer overow error is detected, the data
including the
information of errors is returned, and the error message is indicated on HHT.
Online → Device setup → Detailed setup → Device information → Date
Month and day can be set in a number of 2 gures, Year in 4 gures.
Field devices in multi-drop mode refer to the connection of several eld devices on a
communication single line. Up to 15 eld devices can be connected when set in the
multi-drop mode.
To activate multi-drop communication, the eld device address must be
changed to
a number from 1 to 15.
This change deactivates the 4 to 20 mA output and turns it to 4 mA.
Online → Device setup→ Detailed setup → HART Communication → Poll address
Write protect function is provided to inhibit parameter change. That becomes active by
entering a password in “New password”. Write protect status is released for 10 minutes by entering the
password in “Enable wrt 10 min”.
Hotkey → New password
Enter new password to change state of write.
Hotkey → Enable wrt 10 min
“Enable Write” release write protect status for 10 minutes.