A HART-communicator can communicate with the ROTAMASS RCCT_F3 from the control room, the
ROTAMASS site or any other wiring termination point in the loop, provided there is a minimum load
resistance of 230Ω between the connection and the instrument. To communicate, it must be connected in
parallel with the ROTAMASS
RCCT_F3, the connections are not polarized. The gure below shows the wiring
connections
for direct interface at the ROTAMASS RCCT_F3.
Specications of communication line :
Load resistance : 230 to 600 Ω, for multidrop mode see gure below
Minimum cable size : 24 AWG (0.51 mm diameter)
Cable type :
single pair shielded or multiple pair with overall shield
Maximum twisted pair length : 6,500 ft (2,000 m)
Maximum multiple twisted pair length : 3,200 ft (1,000 m)
Use the following formula to determine cable length for a specic application :
Where : L = length in feet or meters
R = resistance in ohms, current sense resistance
C = cable capacitance in pF/ft or pF/m
C
i
= 50,000 pF
Load resistance and quantity of devices in multidrop mode :
800
700
600
500
400
300
200
100
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Load
resistance [ ]
Quantity of connected field devices
F62.EPS
230
571
500
333
307
285 266
400
444
363
RCCT_F3
HART
Communicator
HART
Communicator
HART
Communicator
Intermediate
terminals
4 to 20mA DC
signal trans-
mission line
Receiving
instrument
Terminal board
Control room
F61.EPS
L =
65x10
6
(RxC)
(C
f
+10,000)
C