The intrinsic safe pulse output is passive and an external power supply with shunt-diode type barrier or
isolation type barrier should be connected.
Maximum voltage : 30 V DC
Maximum current : 100 mA
Example of installation :
Hazardous area
Pout 1 +
Pout 1 -
R barrier
R load
Vin
counter
V out
Ground
Safe area
ROTAMASS
/KF2
F420.EPS
Power supply range : 10.5 V 30 V DC for Not-HART application
Power supply range : 16.75 V 30 V DC for HART application
Load resistance : 20 600 for Not-HART application
Load resistance : 230 600 for HART application
Load resistance vs Power supply voltage :
800
700
600
500
400
300
200
100
0
10 12 14 16 18 20 22 24 26 28 30
Load
resistance [ Ω ]
Power supply voltage [V]
HART communication available range
F419.EPS