Instruction Manual
9-12
All Rights Reserved. Copyright © 2003, Rota Yokogawa
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
- Substitution of components may impair intrinsic safety !
- Only trained persons may use the instrument in industrial location.
- The instrument modication of parts replacement by other than authorized representatives of YOKOGAWA
is prohibited and will void the certication.
- If the cover of the converter case has to be opened, following instructions must be followed:
- Conrm that the power cables to the instrument are disconnected.
- Wait 15 minutes after power is turned off before opening the covers.
- The covers of display side and terminal box are xed with special screws,
please use Hexagonal Wrench to open the covers.
- Be sure to lock the cover with special screw using the Hexagonal Wrench after
tightening the cover (see drawing chapter 4.3).
- Prohibition of specication changes and modications. Users are prohibited from
making any modications of specications or physical conguration, such as adding or changing the
conguration of external wiring ports.
WARNING
1. Remote rack-mount converter RCCR31 must only be installed in safe area !
2. Ex-type RCCR31 and RCCS3 must be connected to the suitable IS earthing system
(see installation diagram). Converter and detector case must have connection to he potential
equalisation facility.
3. Please conrm that the ground terminal on terminal board is rmly connected.
4. For EMC technical reasons the case of the detector is connected to the case of the
converter via the shielding of the interconnecting cable.
Installation diagram :
L/+
N/-
G
Power supply
I/O control
Hazardous area Safe area
I/O
RCCR31
RCCS3
D+
D-
S1+
S1-
S2+
S2-
TP1
TP2
TP3
D+
D-
S1+
S1-
S2+
S2-
TP1
TP2
TP3
COM
Exclusive remote cable RCCY03
F93.EPS
Terminal Board
WARNING