To set the assignments of HART device variables which are reported via
HART Universal Command 3.
Set the assignment of Primary variable (PV).
PV is linked to Analog output 1. Changing of PV will change the
assignment of Analog output 1 and vice versa.
Select:
Set the assignment of Secondary variable (SV).
SV is linked to Analog output 2. Changing of SV will change the
assignment of Analog output 2 and vice versa.
Select:
If Analog output 2 is not available (option /KF2) an extended selection is
available, see “HART Variable list” below.
Set the assignment of Tertiary variable (TV).
TV is linked to Pulse output 1 if is set to In this
case changing of TV will change the assignment of Pulse output 1 and
vice versa.
Select:
If is set to or an extended
selection is available, see “HART Variable list” below . This selection is
stored separately from the selection for “Pulse”.
Set the assignment of Quaternary variable (QV).
QV is linked to Pulse output 2 if is set to In this
case changing of QV will change the assignment of Pulse output 2 and
vice versa.
Select:
If Pulse output 2 is not available (option /KF2 ) or is set to
or an extended selection is available, see “HART
Variable list” below.
This selection is stored separately from the selection for “Pulse”.