User guide

7-4
IM 04L41B01-01E
Timer
Timer used by event action. Used also in the TLOG computation of the computation
function.
* The timer cannot be changed while memory sampling or computation is in progress.
Timer No.
Up to four timers (1 to 4) can be set.
When Using an Absolute Timer
Mode
Select Absolute.
Interval
Select the interval from the available settings between 1min to 24h.
Ref.time
Set the time in the range of hour 0 to hour 23.
When Using a Relative Timer
Mode
Select Relative.
Interval
Set the interval in the range of 00:01 (1 min) to 24:00 (24 hours).
Reset at Math Start
On: Resets the timer when computation is started. The resetting of the timer is not
considered to be a timeout. Even if the timer is used as an event, the action is not
executed.
Match Time Timer
Set the time match condition used in event action.
* The condition cannot be changed while memory sampling or computation is in progress.
Timer number
You can set up to four match time conditions (1 to 4).
7.1 Setting the Event Action Function (Including the remote control function of the /R1 and /PM1 options and