User guide
Measurement Channels and Alarms
IM 04L41B01-01E
3-9
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
• Relay > Relay Action on Ack
You can select the relay output status that is enabled after the AlarmACK operation
from the following two settings. When you use the alarm annunciator function
(release number 3 or later), the setting follows the annunciator sequence.
Settings Description
Normal The relay is deactivated when the alarm ACK operation is executed. If the
condition for activating the alarm output relay is met in the next scan interval, the
relay is activated.
This operation is valid only when the alarm output relay is set to Hold.
Reset The relay is deactivated when the alarm ACK operation is executed. If a new
condition for activating the alarm output relay is met, the relay is activated.
An example of the relay action when alarm ACK is executed is shown below. This
example is for the case when the output relay AND item is set to None.
Normal
Alarm ACK
Alarm output relay
Alarm 2
Alarm 1
Relay is activated in the next scan interval
Activated
Alarm
occurrence
Alarm
occurrence
Deactivated
Reset
Alarm ACK
Relay is activated on the next alarm occurrence
Alarm output relay
Alarm 2
Alarm 1
Activated
Alarm
occurrence
Alarm
occurrence
Deactivated
• Hysteresis > Meas CH
• High/Low
Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm
specied on measurement channels.
Selectable range: 0.0% to 5.0% of the span or scaling width
• Delta High/Low
Sets the hysteresis width of the alarm occurrence/release of the difference high/low
limit alarm specied on measurement channels.
Selectable range: 0.0% to 5.0% of the span
• Hysteresis > Math CH (/M1 and /PM1 options)
Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm
specied on computation channels.
Selectable range: 0.0% to 5.0% of the measurement span
3.5 Setting the Auxiliary Alarm Function










