Instruction Manual

87
IM 04L41B01-02E
Installation and Wiring
Recommended Replacement
Periods for Worn Parts
Setup Items and
Default Values
Communication (Ethernet) > FTP client > FTP connection
Setup Item Selectable Range or Selections Default Value Setting
FTP connection Primary/Secondary Primary
FTP server name 64 characters or less
Port number 0 to 65535 21
Login name 32 characters or less
Password 32 characters or less ******...***
Account 32 characters or less
PASV mode On/Off Off
Initial path 64 characters or less
Communication (Ethernet) > SNTP client
Setup Item Selectable Range or Selections Default Value Setting
Use/Not Use/Not Not
Server name 64 characters or less
Port number 0 to 65535 123
Access interval Off/1h/8h/12h/24h 8h
Access reference time 00:00 to 23:59 00:00
Access timeout 10s/30s/90s 30s
Time adjust on Start action On/Off Off
Communication (Ethernet) > Modbus client > Basic settings
Setup Item Selectable Range or Selections Default Value Setting
Read cycle 125ms/250ms/500ms/1s/2s/5s/10s 1s
Retry interva Off/10s/20s/30s/1min/2min/5min/10min/
20min/30min/1h
2min
Communication (Ethernet) > Modbus client > Modbus server settings
Setup Item Selectable Range or Selections Default Value Setting
Server number 1-8/9-16 1-8
Port
Modbus server name
Unit
No.
0 to 65535
64 characters or less
Auto/Fixed
0 to 255
502
Auto
1
Communication (Ethernet) > Modbus client > Command settings
Setup Item Selectable Range or Selections Default Value Setting
Client command number 1-8/9-16 1-8
1 to 16
First
Last
Server
Regi.
Type
Off/R/R-M/W/W-M/E-M
*3
Depends on the command type.
Depends on the command type.
1/2/3/.../15/16
Numerical value
INT16/UINT16/INT32_B/INT32_L/UINT32_B/
UINT32_L/FLOAT_B/FLOAT_L
Off
1
30001
INT16
Communication (Ethernet) > Password management > KDC connection (/AS1 option)
*3
Setup Item Selectable Range or Selections Default Value Setting
KDC connection Primary/Secondary Primary
KDC server name 64 characters or less
Port number 0 to 65535 88
Setup Items and Default Values