Manual
8
IM 04L41B01-19E
Settings of the DX
Node Address Settings
Press MENU (to switch to setting mode), hold down FUNCfor3s(toswitchtobasic
setting mode), and select the Menutab> Communication (PROFIBUS).
• Node Address
Setanodeaddressintherangeof0to125.
Note
ThenodeaddressofPROFIBUS-DPcanbecheckedontheNetworkInformationScreenofthe
DX.YoucanopentheNetworkInformationScreenbypressingFUNC>Network info softkey.
Others
Status Output (option, /F1 and /F2)
If setting Communication error of the Status Output (/F1 or /F2 option) to On, a relay
outputisprovidedwhenaPROFIBUS-DPcommunicationerroroccurswithintheDX.If
acommunicationerroroccurs,contactyournearestYOKOGAWAdealerforrepairs.
See Section 2.9 of the DX1000/DX1000N User's Manual (IM04L41B01-01E) or DX2000
User's Manual (IM04142B01-01E).
In Basic Setting Mode:
WhentheDXisinthebasicsettingmode,communicationsareavailablebutinput/output
dataisinvalid.
Connection to the PROFIBUS-DP Network