Owner manual
6-17
IM 04L41B01-17E
Specifications
1
2
3
4
5
6
App
Index
Register Description Supplementary Information Type Access Simultaneous
Access
Write Read
410765 Event level switch 1 OFF: 0. ON: 1. INT16 R/W
410766 Event level switch 2 OFF: 0. ON: 1. INT16 R/W
410767 Event level switch 3 OFF: 0. ON: 1. INT16 R/W
410768 Event level switch 4 OFF: 0. ON: 1. INT16 R/W
410765 Event level switch 5 OFF: 0. ON: 1. INT16 R/W
410770 Event level switch 6 OFF: 0. ON: 1. INT16 R/W
410771 Event level switch 7 OFF: 0. ON: 1. INT16 R/W
410772 Event level switch 8 OFF: 0. ON: 1. INT16 R/W
410773 Event level switch 9 OFF: 0. ON: 1. INT16 R/W
410774 Event level switch 10 OFF: 0. ON: 1. INT16 R/W
410775 Event level switch 11 OFF: 0. ON: 1. INT16 R/W
410776 Event level switch 12 OFF: 0. ON: 1. INT16 R/W
410777 Event level switch 13 OFF: 0. ON: 1. INT16 R/W
410778 Event level switch 14 OFF: 0. ON: 1. INT16 R/W
410779 Event level switch 15 OFF: 0. ON: 1. INT16 R/W
410780 Event level switch 16 OFF: 0. ON: 1. INT16 R/W
410781 Event level switch 17 OFF: 0. ON: 1. INT16 R/W
410782 Event level switch 18 OFF: 0. ON: 1. INT16 R/W
410783 Event level switch 19 OFF: 0. ON: 1. INT16 R/W
410784 Event level switch 20 OFF: 0. ON: 1. INT16 R/W
410785 Event level switch 21 OFF: 0. ON: 1. INT16 R/W
410786 Event level switch 22 OFF: 0. ON: 1. INT16 R/W
410787 Event level switch 23 OFF: 0. ON: 1. INT16 R/W
410788 Event level switch 24 OFF: 0. ON: 1. INT16 R/W
410789 Event level switch 25 OFF: 0. ON: 1. INT16 R/W
410790 Event level switch 26 OFF: 0. ON: 1. INT16 R/W
410791 Event level switch 27 OFF: 0. ON: 1. INT16 R/W
410792 Event level switch 28 OFF: 0. ON: 1. INT16 R/W
410793 Event level switch 29 OFF: 0. ON: 1. INT16 R/W
410794 Event level switch 30 OFF: 0. ON: 1. INT16 R/W
410801 Setting function
communication login
The value is 1 only when a user has logged
into the DX setting function through Ethernet
communication. This only applies to DXs with the
/AS1 advanced security option.
INT16 R —
410802 Key login The value is 1 when a user has logged into the
DX through key operations. This only applies to
DXs with the /AS1 advanced security option.
INT16 R —
410803 Login not possible The value is 1 when login through key operations,
login to the setting function through Ethernet
communication, and login through the sending of
the LL command through serial communication
are not possible, because another user is
logged in. This only applies to DXs with the /AS1
advanced security option.
INT16 R —
410804 Individual alarm ACK
channel number
Specifies the alarm released by an individual
alarm ACK operation. The channel and alarm
level are accessed successively. This only applies
to DXs with the /AS1 advanced security option.
INT16 W
410805 Individual alarm
acknowledgment alarm
level
INT16 W
Notation used in the Access column
W: Writable
R: Readable
If you read a write-only (W) register, zero is always read.
If you write to a read-only (R) register, an error occurs.
Notation used in the Simultaneous access column
Blank:
Indicates a range of registers that can be written to or read from simultaneously.
You cannot simultaneously access across a solid line.
-: Not accessible.
6.3 Modbus Protocol Specifications