Register Description Supplementary Information Type Access Simultaneous
Access
Write Read
410611 Free message writing Message number (1 to 10) INT16 W
410612 Message write destination INT16 W
• When the multi batch function is not in use
0: All groups. 1 to 36: Specified group number.
• When the multi batch function is in use
0: All groups of a specified batch number
(410613)
1 to 12: Specified group number
410613 Batch number designation for multi batch: 1 to 12
(Valid only when the multi batch function is
available. Any value when the multi batch function
is not available)
INT16 W
410614 to
410631
Free message
Up to 18 registers (up to 35 characters with '\0'
termination).
The message must be 32 characters or less.
STR36 W
410632 to
410680
(Reserved) Free
message
- - -
410681 Batch 1 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410682 Batch 2 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410683 Batch 3 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410684 Batch 4 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410685 Batch 5 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410686 Batch 6 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410687 Batch 7 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410688 Batch 8 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410689 Batch 9 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410690 Batch 10 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410691 Batch 11 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
410692 Batch 12 memory start
and stop
Stop: 0. Start: 1. INT16 R/W
6.3 Modbus Protocol Specifications