Owner manual

6-10
IM 04L41B01-17E
Hold Register (shared with the Modbus slave function)
Common Items
The client device can read and write to the hold registers.
Communication input data is an option (/M1, /PM1).
External input channels are DX2000 option (/MC1).
When Writing
Communication input data can be handled on a computation channel by including
the data in the equation of a DX computation channel.
External input channel data can be handled on an external input channel.
Details
Details
Hold Register Data Data Type
400001 Communication input data C01
16-bit signed integer
| |
400060 Communication input data C60
Precautions to be taken when the client device reads the data
The communication input data of the DX is floating point type, but the data is converted to
signed 16-bit integer when the data is read.
Precautions to be taken when the client device writes the data
Only data in signed 16-bit integer type can be written. Floating point values cannot be
written.
400301 Lower bytes of communication input data C01
32-bit floating point
400302 Higher bytes of communication input data C01
| |
400419 Lower bytes of communication input data C60
400420 Higher bytes of communication input data C60
Precautions to be taken when the client device writes the data
Input range: –9.9999E29 to –1E–30, 0, 1E–30 to 9.9999E29
If values outside this range are used on a computation channel, a computation error
occurs.
401001 External input channel write register 201
16-bit signed integer
| |
401240 External input channel write register 440
Precautions to be taken when the client device writes the data
Only data in signed 16-bit integer type can be written.
The measurement range and unit are set using the external input channels. The decimal
point position is determined by the Span_L settings.
6.3 Modbus Protocol Specifications