Owner manual

6-8
IM 04L41B01-17E
Input Register (shared with the Modbus slave function)
Common Items
The client device can only read the input registers.
Decimal position and unit are not included. Specify them on the client device.
External input channels are DX2000 option (/MC1).
Details
Input Register Data Data Type
300001 Measured data of measurement channel 001
16-bit signed integer
| |
300048 Measured data of measurement channel 048
There is no decimal position information.
301001 Alarm status of measurement channel 001
Bit string
| |
301048 Alarm status of measurement channel 048
Register structure and alarm status values
2 1 4 3
4 bits 4 bits 4 bits 4 bits
4-bits
value Meaning
0 No alarm
1 High limit alarm
2 Low limit alarm
3 Difference high limit alarm
4 Difference low limit alarm
5 High limit on rate-of-change alarm
6 Low limit on rate-of-change alarm
7 Delay high limit alarm
8 Delay low limit alarm
Alarm level
Alarm status
302001 Lower bytes of the computed data of computation channel 101
32-bit signed integer
302002 Higher bytes of the computed data of computation channel 101
| |
302119 Lower bytes of the computed data of computation channel 160
302120 Higher bytes of the computed data of computation channel 160
Register structure
Example: Channel 101
Higher bytes Lower bytes
Register 302002
Computed data
Register 302001
There is no decimal position information.
303001 Alarm status of computation channel 101
Bit string
|
303060 Alarm status of computation channel 160
Register structure and alarm status values: Same as the alarm status of the
measurement channels.
304001 Measured data of external input channel 201
16-bit signed integer
| |
304240 Measured data of external input channel 440
There is no decimal position information.
305001 Alarm status of external input channel 201
Bit string
| |
305240 Alarm status of external input channel 440
Register structure and alarm status values: Same as the alarm status of the
measurement channels.
6.3 Modbus Protocol Specifications