Owner manual
3-42
IM 04L41B01-17E
Example Start the e-mail transmission function.
EM0
Description
T
o use the e-mail transmission function, you
must configure the Ethernet interface, set e-mail
addresses, and enter the contents you want to
transmit.
CU Recovers Modbus manually
Syntax
CU p1<terminator>
p1
Communication type
0
Modbus client (Ethernet)
1
Modbus master (serial)
YO Loads a setup file for basic
setting mode
Syntax
YO p1,p2,p3<terminator>
p1
N
a
m
e of the file to load (up to 32 characters)
p2
Medium
0
CF slot
1
USB
p3
What to load (0 to 2)
0
Basic setting mode and setting
mode settings
1
Basic setting mode settings
(except for login settings) and
setting mode settings
2
Login settings
Example
Only load the CONFIG1 login settings from the
CF card.
YOCONFIG1,0,2
Description
• Do not include the extension when specifying
the file name.
•
Y
ou can set p2 to 1 on models with the /USB1
USB interface option.
•
If you omit parameter p2, the medium is set to
CF slot.
• p3 is only valid on models with the /AS1
advanced security option.
• Omitting p3 is the same as setting it to 0.
YC Clears measured and computed
data and initializes setup data
Syntax
YC p1<terminator>
p1
The types of data to be initialized and
cleared
0
Basic setting mode settings,
setting mode settings, measured
and computed data, custom
display screen setup data, and log
data
(“Clear 1” on the DX)
1
Setting mode settings, measured
and computed data, custom
display screen setup data, and log
data
(“Clear 2” on the DX)
2
Measured and computed data,
custom display screen setup data,
and log data
(“Clear 3” on the DX)
Example
Perform “Clear 3” on the DX.
YC2
Description
This command is invalid on models with the /AS1
advanced security option.
IR Resets a relative timer
Syntax
IR p1<terminator>
p1
Number of the timer to reset
0
All timers
1
,
2
, ... Timer number
Example Reset timer 2.
IR2
Description
Set p1 by referring to the table in section 3.3.
MA Resets a match time timer
Syntax
MA p1<terminator>
p1
Number of the timer to reset
1
,
2
, ... Timer number
Example Reset match time timer 2.
MA2
Description
•
Set p1 by referring to the table in section 3.3.
•
This command is valid for expired match time
timers whose operation is set to single.
CW Sets an event switch
Syntax
CW p1,p2,p3<terminator>
p1
Type of operation (LEVEL, EDGE)
p2
Event switch number (1 to 30)
p3
On/off (OFF, ON)
Parameter p3 is valid when p1 is set to
LEVEL.
Example Set event level switch 2 to ON.
CWLEVEL,2,ON
LR Loads custom display screens
Syntax
LR p1,p2,p3,p4<terminator>
p1
Medium (fixed at 0)
0
External CF card
p2
Screen range (ALL, SELECT)
ALL
All screens
Loads all of the custom display
screens that are stored in the
specified directory.
SELECT
A specific screen
Loads a specific custom display
setup file to the screen that you
specify.
When p2 is set to
ALL
p3
Name of the directory to load from (up to 20
characters)
3.5 Control Commands