p10
Tag prioritized display (ON, OFF)
Example Enable automatic display switching, switch to the
group display, turn on the scale display, and turn
off the digital display.
UD4,ON,GROUP,ON,OFF
Description
Parameter p2 is valid for the trend, digital, and
bar graph displays. Use the SE command to
set the switching interval.
Parameters p3 to p7 are valid for the trend
display
.
When multi batch /BT2 is in use, you cannot
use this command in batch overview mode.
To switch the operation screen mode
Syntax
UD p1,p2,p3<terminator>
p1
Display type (5)
p2
Operation screen mode (COMMON,
BATCH)
COMMON
Batch overview mode
BATCH
Batch single mode
p3
Batch group number
Description Y
ou can use this command when multi batch
/BT2 is in use.
Parameter p3 is valid when p2 is set to
BATCH.
Set parameter p3 by referring to the table in
section 3.3.
PS Starts or stops recording
Syntax
PS p1,p2<terminator>
p1
Recording start or stop
0
Start
1
Stop
p2
Batch group number
0
All groups
1
,
2
, ... Batch group number
Example Start recording.
PS0
Description When you start recording, the DX records
display
, event, and report data to the internal
memory.
Parameter p2 is valid
when multi batch /BT2 is
in use. If you omit p2, it is the same as setting
p2 to zero.
When the /AS1 advanced security option is
in use and the DX is in setting mode, it will
not start recording even if you send a PS0
command.
Set parameter p2 by referring to the table in
section 3.3.
AK Clears alarm output
(acknowledge alarms)
Syntax
AK p1,p2,p3<terminator>
p1
Executes alarm acknowledge (0)
0
Alarm acknowledge
1
Individual alarm acknowledgment
2
Resets alarm display
p2
Channel number
p3
Alarm level (1 to 4)
Example Clear alarm output (acknowledge alarms).
AK0
Description If you set p1 to 2 when annunciator mode is
on and the sequence is not ISA-M, an error
occurs.
If you send this command with p1 set to 2
before acknowledging the alarms, nothing
happens.
Set p2 by referring to the table in section 3.3.
p2 and p3 are only valid when p1=1.
The
setting p1=1 is only valid on models with the
/AS1 advanced security option.
EV Executes manual sample,
generates a manual trigger, takes
a snapshot, or causes a timeout
Syntax
EV p1,p2<terminator>
p1
T
ype of operation
0
Executes manual sampling.
1
Generates a manual trigger.
2
Takes a snapshot.
3
Causes a timeout in display data.
4
Causes a timeout in event data.
p2
Batch group number
0
All groups
1
,
2
, ... Batch group number
Example
Execute manual sampling.
EV0
Description
EV1 is only valid when the key trigger is set to
ON using the event data sampling condition
command (TE command).
This command is
equivalent to a key trigger.
When multi batch /BT2 is in use, p2 is valid
w
h
en p1 is set to 3 or 4. If you omit p2, it is the
same as setting p2 to zero.
Set parameter p2 by referring to the table in
section 3.3.
CL Executes manual SNTP
Syntax
CL p1<terminator>
p1
Executes manual SNTP(0)
Example
Synchronize the clock.
CL0
CV Switches between normal and
secondary trend interval
Syntax
CV p1<terminator>
p1
Trend interval (0, 1)
0
Switches to the normal trend
interval
1
Switches to the secondary trend
interval
3.5 Control Commands