Owner manual
3-33
Commands
IM 04L41B01-17E
1
2
3
4
5
6
App
Index
Query
BD[p1]?
Example
Set the channel 001 alarm delay to 120 s.
BD001,120
Description •
Set p1 by referring to the table in section 3.3.
•
The p2 unit is seconds.
On DXs with the /AS1 Advanced Security Option
Syntax
BD p1,p2,p3<terminator>
p1
Measurement, computation, or external
input channel number
p2
Alarm delay (1 to 3600)
p3
Unit (SEC, HOUR)
Query
BD[p1]?
Example
Set the channel 001 alarm delay to 2 hours.
BD001,2,HUOR
Description •
Set p1 by referring to the table in section 3.3.
•
When p3 = HOUR, you can set p2 to a value
from 1 to 24.
NC Sets a comment text field
Syntax
NC p1,p2<terminator>
p1
Comment text field number
p2
Comment string (up to 32 characters)
Query
NC[p1]?
Example
Set comment text field 30 to “P1 end.”
NC30,P1
end
Description Set parameter p2 by referring to the table in
section 3.3.
NB Sets a comment text block
Syntax
NB p1,p2,p3,p4,p5,p6<terminator>
p1
Comment text block number
p2
Comment text field number of line 1
p3
Comment text field number of line 2
p4
Comment text field number of line 3
p5
Comment text field number of line 4
p6
Comment text field number of line 5
Query
NB[p1]?
Example
Set comment text block 5’
s lines 1, 2, and 3 to
comment text field 10, 1
1, and 14, respectively.
NB5,10,11,14
Description
Set parameters p1 through p6 by referring to the
table in section 3.3.
NW Sets an annunciator display
Syntax
NW p1,p2,p3 p4,p5<terminator>
p1
Display window number
p2
On/Off (ON, OFF)
p3
Measurement, computation, or external
input channel number
p4
Alarm level (1 to 4, ALL)
p5
Label (comment text block number)
Query
NW[p1]?
Example Assign the channel 2’s alarm level 1 alarm to
display window 4 and display the comment text
block 3 label.
NW4,ON,2,1,3
Description
•
Set parameters p1 and p5 by referring to the
table in section 3.3.
•
Y
ou cannot use this command when the
annunciator mode is set to Of
f (using the WU
command).
NG Sets the Web report layout
Syntax
NG p1,p2,p3<terminator>
p1
Report page number (1 to 10)
p2
Creation (ON, OFF)
p3
Report title string (up to 64 characters)
Query
NG[p1]?
Example
Set the title of report page 2 to “Factory 3.”
NG2,ON,Factory
3
Description • You can use this command on models with the
/M1 or /PM1 math option.
•
Y
ou cannot use this command if:
•
The Web server function is set to Not (using
the WS command).
• The operator and monitor pages are both
set to Off (using the WW command).
NH Sets Web report layout details
Syntax
NH p1,p2,p3,p4,p5,p6<terminator>
p1
Report page number (1 to 10)
p2
Item number (1 to 10)
p3
Creation (ON, OFF)
p4
Report channel number (R01 to R60)
p5
V
alue (MIN, MAX,
A
VE, SUM, INST)
p6
Item name string (up to 16 characters)
Query
NH[p1,[p2]]?
Example Assign the title “Average” to report page 2 item 6,
and display the average of the measured values
for the channel assigned to report channel R07.
NH2,6,R07,AVE,Average
Description
• You can use this command on models with the
/M1 or /PM1 math option.
• The selectable values for p4 varies depending
on the model.
•
Y
ou cannot use this command if:
•
The Web server function is set to Not (using
the WS command).
• The operator and monitor pages are both
set to Off (using the WW command).
FR Sets the interval for acquiring
data to the FIFO buffer
Syntax
FR p1<terminator>
p1
1 (fixed)
p1
FIFO acquisition interval (25MS, 125MS,
250MS, 500MS, 1S, 2S, 5S)
3.4 Setting Commands