Owner manual

3-28
IM 04L41B01-17E
TG Sets a color scale band
Syntax
TG p1,p2,p3,p4,p5<terminator>
p1
Measurement, computation, or external
input channel number
p2
Area (OFF
, IN, OUT)
p3
Color (AUTO or 24 colors (see NL; sets a
trip line))
p4
Lower display position limit
p5
Upper display position limit
Query
TG[p1]?
Example
Set the channel 005 color scale band to the
range from -1.0000 to 0.5000 V (2-V range), and
set the color to green.
TG005,IN,GREEN,-10000,5000
SQ Sets the LCD brightness and the
screen backlight saver
Syntax
SQ p1,p2,p3,p4<terminator>
p1
LCD brightness
1
to
8
DX1000
1 to 6
DX2000
p2
Screen backlight saver type
OFF
Disables the saver function.
DIMMER
Dims the backlight
TIMEOFF
Turns off the backlight
p3
Amount of time until the DX switches to
saver mode
1
M
I
N, 2MIN, 5MIN, 10MIN, 30MIN,1H
p4
Event that causes the DX to return from
saver mode
KEY
Pressing of a key
KEY+ALM
Pressing of a key or an alarm
occurrence
Query
SQ?
Example Set the LCD brightness to 2 and the screen
backlight saver type to dimmer. Set the amount
time of until the DX switches to saver mode to
5 minutes and the event that causes the DX to
return from saver mode to pressing of a key
.
SQ2,DIMMER,5MIN,KEY
Description
If p2 is set to OFF, do not set p3 or p4.
TC Sets the background color
Syntax
TC p1,p2<terminator>
p1
Screen (WHITE, BLACK)
p2
Historical trend screen (WHITE, CREAM,
LIGHTGRAY, BLACK)
Query
TC?
Example
Set the screen background to black and the
historical trend screen background to cream.
TCBLACK,CREAM
TP Sets automatic display group
switching
Syntax
TP p1<terminator>
p1
Auto switching interval (5S, 10S, 20S, 30S,
1MIN)
Query
TP?
Example
Switch between display groups at 5-s intervals.
TP5S
NF Sets the favorite key operation
Syntax
NF p1,p2,p3<terminator>
p1
T
ype of operation
FAVORITE
Operates as a favorite key.
HISTORY
Operates as a key for switching
to the historical display
.
p2
Display group
SAVED
Displays the display group that
was selected when you registered
the favorite key
CURRENT
Displays the current display group
p3
Historical trend time axis zoom
SAVED
Displays the historical trend using
the time axis zoom setting that
was used when you registered the
favorite key
CURRENT
Displays the historical trend using
the current time axis zoom setting
Query
NF?
Example
Set the favorite key as a key used to switch to
the historical display.
NF,HISTORY
Description
Parameters p2 and p3 are valid when p1 is set to
FAVORITE.
TR Sets the automatic switching
back to default display
Syntax
TR p1<terminator>
p1
Automatic return time limit (OFF
, 1MIN,
2MIN, 5MIN, 10MIN, 20MIN, 30MIN, 1H)
Query
TR?
Example
Set the automatic return time limit to 5 minutes.
TR5MIN
TQ Sets a timer
When p2 is set to OFF (no timer)
Syntax
TQ p1,p2<terminator>
p1
T
imer number
p2
Timer type (OFF)
When p2 is set to ABSOLUTE (absolute timer)
Syntax
TQ p1,p2,p3,p4<terminator>
p1
T
imer number
p2
Timer type (ABSOLUTE)
p3
Ti
m
e interval (1MIN to 6MIN, 10MIN, 12MIN,
15MIN, 20MIN, 30MIN, 1H to 4H, 6H, 8H,
12H, 24H)
3.4 Setting Commands