Owner manual

3-7
IM 04L41B01-17E
Commands
1
2
3
4
5
6
App
Index
Basic Setting Commands
In order to activate the settings that are changed using the basic setting commands,
the settings must be saved using the YE or XE command. Make sure to save
the settings before changing from the basic setting mode to the operation mode.
Otherwise, new settings will not be activated.
The settings
that are returned in response to a query in basic setting mode contain the
new settings even if they are not saved. However, the new settings are not activated
unless they are saved. If the settings are cleared or if you change from basic setting
mode to operation mode before saving the settings, the settings that are returned
in the response to a query contain the settings that were used before they were
changed.
Note
The settings that are changed using the
YA, YK, RU, YQ, YS, YB, YD, WS, WW,
and
WQ
commands are activated after saving the new settings using the
XE
command and
restarting the DX.
When you execute the
YE
or
YO
command, communication is disconnected. Commands
listed after the YO or YE command are ignored.
Group
Command
Function Execution Administrator User Page
Name Mode
WU
Sets the environment Basic setting mode Y
es No 3-45
WE
Sets calibration management
Basic setting mode
Yes
No
3-47
WO
Sets alarm and DO settings
Basic setting mode Y
es No 3-48
WH
Sets alarm hysteresis Basic setting mode Y
es No 3-48
XV
Sets the scan interval and A/D integral time Basic setting mode
Yes No 3-48
XB
Sets burnout detection Basic setting mode Y
es No 3-49
XJ
Sets RJC Basic setting mode Y
es No 3-49
XM
Sets memory sampling conditions Basic setting mode Y
es No 3-49
XT
Sets the temperature unit Basic setting mode Y
es No 3-49
RF
Sets key lock Basic setting mode Y
es No 3-49
RN
Sets basic key login Basic setting mode Y
es No 3-50
RP
Sets user limitations Basic setting mode Y
es No 3-50
RO
Sets the type of report and when to create reports Basic setting mode Y
es No 3-51
RM
Sets a report channel Basic setting mode Y
es No 3-52
XG
Sets the time zone Basic setting mode Yes No 3-52
XN
Sets the date format Basic setting mode Y
es No 3-52
YB
Sets host information Basic setting mode Y
es No 3-52
YD
Sets network parameters Basic setting mode Y
es No 3-53
YA
Sets the IP address, subnet mask, and default gateway Basic setting mode
Yes No 3-53
YK
Sets keepalive Basic setting mode Y
es No 3-53
RU
Sets DNS parameters Basic setting mode Y
es No 3-53
WS
Sets a server Basic setting mode Y
es No 3-53
WW
Sets Webpage parameters Basic setting mode
Yes No 3-53
YQ
Sets communication timeout Basic setting mode Y
es No 3-53
YT
Sets FTP transfer timing Basic setting mode
Yes No 3-54
YU
Sets what kind of information to send using e-mail Basic setting mode Y
es No 3-54
YV
Sets an e-mail recipient address Basic setting mode Y
es No 3-55
YW
Sets the e-mail sender address Basic setting mode Y
es No 3-55
YX
Sets the e-mail SNTP server name Basic setting mode
Yes No 3-55
YJ
Sets the Modbus client’s destination server Basic setting mode
Yes No 3-55
YP
Sets basic Modbus client settings Basic setting mode Y
es No 3-55
YR
Sets the Modbus client’s transmit command Basic setting mode
Yes No 3-55
WB
Sets SNTP client parameters Basic setting mode
Yes No 3-56
WC
Sets the SNTP operation when memory start is Basic setting mode
Yes No 3-56
executed
YS
Sets the serial interface Basic setting mode Y
es No 3-56
3.2 A List of Commands