Owner manual

2-13
IM 04L41B01-17E
Using the Serial Interface
1
2
3
4
5
6
App
Index
E-M: Read to the communication input data (32-bit floating point type) from the
server/write the custom display value to the server (release numbers 4 and
later).
R can be selected on DX2000s with the external input channel (/MC1) installed.
R-M, W-M, and E-M can be selected on models with the computation function
(/M1 or /PM1) option installed.
First/Last (DX’s channel numbers)
Enter the first and last channel numbers of input/output. The range of channels that
you can enter varies depending on the command type as follows:
R: 201 to 440, R-M: C01 to C60, W: 1 to 48, W-M: 101 to 160, E-M: C01 to C60
Address
Enter the address of the slave device in the range of 1 to 247.
Regi.
Set the register number of the slave.
For an input register, select in the range of 30001 to 39999 and 300001 to 365536.
For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.
The register numbers you can specify vary depending on the command type. See
section 6.3.
Type
Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT_L, FLOAT_B, or
FLOAT_L.
The register numbers you can specify vary depending on the command type. See
section 6.3.
Examples of Setting Commands
See page 1-36.
Checking the Modbus Operating Status
Displaying the Modbus Operating Status
Press DISP/ENTER and select INFORMATION > MODBUS MASTER.
Note
To display the MODBUS MASTER on the screen selection menu, you need to change the
setting using the menu cutomize function. Operate as follows:
Press
MENU
(to switch to setting mode), and select the
Menu
tab >
Menu customize
>
Display menu.
1. Select INFORMATION > MODBUS MASTER
.
2. Press the View soft key.
Address for a slave device
Register number
DX channels
Detail code
Status lamp
Cursor to select a command
(Used when resuming command transmission
to a slave device using the front panel keys)
Communication condition
2.6 Using the Modbus Master Function