<A1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION>
A1-8
IM 01R01B30-00E-E 5th edition February 01, 2013 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
Table 7: Summary for RAKD ([V3]) with standard limit switches
7
– Failure rate
Prole 2 Prole 4
Fail Safe Detected (λSD) 0 FIT 0 FIT
Fail Safe Undetected (λSU) 262 FIT 367 FIT
Fail Dangerous Detected (λDD) 4 FIT 19 FIT
Fail Dangerous Undetected (λDU) 203 FIT 295 FIT
SFF
4
56.7% 56.7%
MTBF 226 years 153 years
SIL AC
5
SIL1 SIL1
Safety metrics according to ISO 13849-1
6
:
MTTF
d
(years) 551 364
DC 2% 6%
Category (CAT) CAT 1 CAT 1
Performance Level (required) PL
r
= c PL
r
= c
Performance Level (calculated) 2.07E-07 1/h 3.14E-07 1/h
T[Proof] = 1 year T[Proof] = 5 years T[Proof] = 10 years
PFDAVG = 9.69E-04 PFDAVG = 4.49E-03 PFDAVG = 8.89E-03
3
The switching contact output is connected to a fail-safe NAMUR amplier (e.g. Pepperl+Fuchs KF**-
SH-Ex1). The failure rates of the amplier are not included in the listed failure rates
4
The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure
Fraction. The number listed is for reference only.
5
SIL AC (architectural constraints) means that the calculated values are within the range for hardware
architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements
are fullled.
6
Depending on the application and possible external diagnostics a higher DC
D
and therefore also a
higher category might be possible to achieve.
7
The switching contact output is connected to a standard switching amplier (e.g. Pepperl+Fuchs KF**-
SR2-Ex*.W). The failure rates of the amplier are not included in the listed failure rates.