Configuring the Recorderr
1
2
3
4
Index
A/D Integrate, Temperature, Batch, Aux, and Math Exception
Click here (or choose [Setting] > [SET [Basic] Setting] 
> [A/D Integrate]/[Temperature]/[Batch]/[Aux]/[Math Exception])
Displayed on models with the computation 
function (/M1 option).
On the pen model, [Filter] is displayed.
A/D Integrate (Integration Time of the A/D Converter)
50 Hz:  Sets the time to 20 ms.
60 Hz:  Sets the time to 16.7 ms.
Auto:  Set to the integration time synchronized to the power supply 
frequency (20 ms or 16.7 ms).
100 ms (dot model): Sets the integration time to 100 ms. 
The scan interval is set to 2.5 s.
Temperature
Sets the unit of temperature measurements using thermocouples and RTDs.
C:  Celsius
F:  Fahrenheit
Batch (/BT1 Option)*
*  Function available on recorders with firmware version 1.31 or later.
•  Batch
  Use: Enables start printout, end printout, and batch name.
•  Digit of lot number
  Sets the number of digits of the lot number.
•  Dual Comment
  Use: Enables start printout 2 and end printout 2.
Aux
•  Moving Ave (Dot Model)
  Select Use to enable the setting of the sampling count of the moving average for the 
measurement channels.
•  Filter (Pen Model)
  Select Use to enable the setting of the lter constant for the measurement channels.
•  Partial
  Select Use to enable the setting of the boundary position and boundary value of the 
partial expanded recording function for measurement channels and computation 
channels.
2.7 Setting the Items in Basic Setting Mode