User Manual
IM 04P01B01-01E 
2-10
Wiring Procedure
1.
  Turn OFF the recorder and remove the terminal cover.
2.
  Connect the input/output signal wires to the terminals.
Philips
screwdriver
Crimp-on lug with 
insulation sleeves
3.
  Replace the terminal cover and fasten it with screws.
The proper torque for tightening the screws is 0.6 N•m.
Alarm Output Relay Terminals and FAIL/Chart End Output Relay Terminals
C
NO
NC
NO (Normally Opened), C (Common), NC (Normally Closed)
•  Relay Contact Output Specifications
  Output type:      Relay
  Contact rating:    250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (resistive load)
  Dielectric strength:   1500 VAC at 50/60 Hz for one minute (between output 
terminals and the ground terminal)
Remote Control Input Terminals
1 2 3
4 5
C
1 2 3
4 5
C
C
1 to 5
Internal circuit
Input type:
Photocoupler isolation
 Shared common (C)
Allowable input voltage:
5 VDC
5V
1 to 5 (Remote control input terminals), C (Common)
Transistor input 
(open collector)
Relay contact input
(voltage-free contact)
•  Relay Contact Input/Transistor Input Specifications
  Input signal:  •  Voltage-free contact: Contact closed at 200 Ω or less and 
contact open at 100 kΩ or greater
    •  Open collector:
 0.5 V or less (30 mADC) when turned ON, 
leakage current of 0.25 mA or less when turned OFF
  Dielectric strength:   500 VDC for one minute between input terminals and the 
ground terminal
Note
To reduce noise, use a shielded cable for the wiring of the remote control input terminals. 
Connect the shield to the ground terminal of the recorder.
2.4 Optional Terminal Wiring